| Plan Review Notes For Permit 11030172 |
| Permit Number |
11030172 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-03-15 09:25:37 | PLANS DENIED | | | HOOD AND WALK IN COOLERS MUST HAVE SEPARATE PLANS | | | ,PERMIT AND APPLICATION. | | | CONDENSATE DRAIN FOR THREE TON A/C CAN NOT TIE IN TO | | | WASTE WATER SECTION 90-125 CITY CODE. | | | REFER TO SECTION 606.2.1 SUPPLY AIR 2007 FBC (M) SMOKE | | | DETECTORS SHALL BE INSTALLED ON SUPPLY. | | | REFER TO SECTION 606.3 INSTALLATION 2007 FBC (M) . | | | PLEASE PROVIDE THE LENGTH OF TEK SCREW FOR RTU MOUNTING | | | DETAIL. | | | PLEASE PROVIDE A DETAIL FOR CURB TO ROOF TIE DOWN. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|