| 2011-03-28 13:22:36 | PALM BEACH DRAMAWORKS |
| | PERMIT NUMBER 11030136 |
| | |
| | 1) PLEASE PROVIDE SEPARATE PLANS AND PERMIT FOR THE |
| | RELOCATION OF THE GAS METER AND APPURTENANT PIPING TO |
| | THE CONSTRUCTION SERVICES DEPARTMENT. |
| | |
| | 2) NO DAMAGE IS TO OCCUR TO THE EXISTING FIRE SPRINKLER |
| | SYSTEM. |
| | |
| | 3) THE "ACCESS DOOR TO REMAIN" FOR THE ROOF LOCATED |
| | NEAR THE STAIRS IS TO BE MARKED NO EXIT. |
| | |
| | 4) ADDITIONAL EXIT SIGNS APPEAR TO BE NEEDED ON THE |
| | FIRST LEVEL. IN SOME CASES BLIND CORNERS EXIST ABSENT |
| | OF EXIT SIGNS. (LS100) ALSO EXIT SIGNS APPEAR TO BE |
| | MISSING ALONG THE NARCISSUS AVENUE SIDE. |
| | |
| | 5) EXIT SIGN MISSING FROM EXIT DOOR LEADING TO ALLY, |
| | NORTH SIDE. (LS100) |
| | |
| | 6) ADDITIONAL EXIT SIGNS APPEAR TO BE NEEDED ON THE |
| | SECOND LEVEL. PLEASE REVIEW. |
| | |
| | 7) ELEVATOR WARNING SIGNS NEEDED AT EACH ELEVATOR |
| | OPENING. |
| | |
| | 8) ASTERICS SHOWN ON THE SECOND FLOOR ACCESSIBILITY |
| | PLAN DEPICTS WHAT. |
| | |
| | 9) PLEASE FURTHER EXPLAIN TRIPPING HAZARD NOTE ON SHEET |
| | A100. WHAT IS THE ELEVATION DIFFERENCE. |
| | |
| | 10) THE EXISTING FIRE DEPARTMENT CONNECTION SHALL BE |
| | INSPECTED TO ENSURE PROPER OPERATION. BOTH CONNECTIONS |
| | SHALL FREELY SWIVEL AND CAPS ARE TO BE MAINTAINED. |
| | |
| | 11) SOFFITS SHALL NOT INTERFERE WITH THE OPERATION OF |
| | ANY AUTOMATIC FIRE SPRINKLER HEADS. |
| | |
| | 12) HOW WILL EXIT ACCESS BE MAINTAINED IN COSTUME SHOP |
| | 209 DISPLAYED ON THE SECOND FLOOR. |
| | |
| | 13) PLEASE PROVIDE MORE DETAILS ON INTERSTITIAL SPACE |
| | ABOVE NEW ADMINISTRATIVE OFFICE. WHAT IS PRESENT, IS |
| | THERE ACCESS, AND IS THIS AREA PROTECTED BY AUTOMATIC |
| | FIRE SPRINKLERS. (TECHNICAL LEVEL CATWALK PLAN) |
| | |
| | 14) PLEASE INDICATE PRESCRIPTIVE STRENGTH REQUIREMENTS |
| | FOR NEW CATWALKS, HANGERS, AND HANDRAILS SHOWN ON THE |
| | TECHNICAL LEVEL/CATWALK PLAN. PLEASE INDICATE HEIGHTS |
| | OF NEW HANDRAILS. |
| | |
| | 15) SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE |
| | SPRINKLER SYSTEM REMODELING. |
| | |
| | 16) SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE |
| | SPRINKLER SYSTEM REMODELING. |
| | |
| | 17) EXISTING EXIT SIGNS AND EMERGENCY LIGHTS ARE TO BE |
| | INSPECTED TO ENSURE PROPER OPERATION. |
| | |
| | 18) ADDITIONAL SIGNALING FIRE ALARM DEVICES APPEAR TO |
| | BE NEEDED. NO FIRE ALARM DEVICES ARE PRESENT IN |
| | REHEARSAL SPACE 201. SOME BATHROOMS ARE ABSENT OF |
| | SIGNALING APPLIANCES. |
| | |
| | 19) ALL HANDRAILS AND GUARDRAILS TO MEET THE |
| | PRESCRIPTIVE STRENGTH REQUIREMENTS. |
| | |
| | 20. PLEASE PROVIDE FLAME-SPREAD DETAILS FOR TECTUM |
| | FINALE ACOUSTIC WALL PANEL. |
| | |
| | 21. SECURITY DEVICES INSTALLED ON DOORS SHALL NOT |
| | INTERFERE WITH ANY EXITING. |
| | |
| | 22. ALL NEW FIRE WALLS ARE TO BE PROPERLY IDENTIFIED. |
| | |
| | 23. NO COMBUSTIBLES ALLOWED IN THE RETURN AIR PLENUM AS |
| | DESCRIBED ON THE PLANS. |
| | |
| | 24. ALL NEW FIRE DAMPERS ARE TO BE DROP TESTED TO |
| | ENSURE PROPER FUNCTION. |
| | |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |
| | (561) 804-4724 PHONE |
| | (561) 804-4774 FAX |