| Plan Review Notes For Permit 11030115 |
| Permit Number |
11030115 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-03-07 09:05:17 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C AND | | | THE ENGINEERING THAT WAS SUBMITTED IS FOR EXPOSURE B. | | | PLEASE CORRECT. | | | | | | 2) THE INFORMATION ON THE WINDOW/SHUTTER DIAGRAM SHEET | | | IS INCORRECT. THE WORK IS BEING DONE TO A CONDO UNIT | | | LOCATED WITHIN A TWO STORY BUILDING WITH A FLAT ROOF. | | | THE DIMENSIONS OF THE BUILDING ARE APPROXIMATELY 46 | | | FEET WIDE AND 150 FEET IN LENGTH. PLEASE CORRECT. | | | | | | 3) REVISE THE WINDOW AND DOOR INFORMATION SHEET TO | | | REFLECT THE INCREASED PRESSURES OF EXPOSURE C. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|