Plan Review Notes
Plan Review Notes For Permit 11030102
Permit Number 11030102
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-03-15 17:47:01306 CLEMATIS STREET
 PERMIT #11030102
 MASTER #11010398
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 SIGNIFICANT FLOOR PLAN CHANGES HAVE OCCURED UNDER THE
 MASTER PERMIT THAT WILL EFFECT THE SPRINKLER DESIGN AND
 HYDRAULIC CALCULATIONS.
  
 PROVIDE LOCKABLE KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 PROVIDE PERMANENT WEATHERPROOF SIGNAGE FOR FIRE
 DEPARTMENT CONNECTION.
  
 VERIFY TAMPER SWITCHES ARE SUPERVISING THE CONTROL
 VALVES ON THE BACKFLOW PREVENTER.
  
 VERIFY EXISTING SPRINKLERS NOT BEING RELOCATED ARE
 QUICK RESPONSE TYPE.
  
 REROUTE EXISTING FOUR INCH CROSS MAIN TO AVOID STAIR
 ENTRY AND EXIT PENETRATIONS.
  
 A CEILING HEIGHT OF 14 FEET CORRESPONDS TO A HYDRAULIC
 AREA OF AT LEAST 990 SQUARE FEET.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  
  