| Plan Review Notes For Permit 11030102 |
| Permit Number |
11030102 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-03-15 17:47:01 | 306 CLEMATIS STREET | | | PERMIT #11030102 | | | MASTER #11010398 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | | | | SIGNIFICANT FLOOR PLAN CHANGES HAVE OCCURED UNDER THE | | | MASTER PERMIT THAT WILL EFFECT THE SPRINKLER DESIGN AND | | | HYDRAULIC CALCULATIONS. | | | | | | PROVIDE LOCKABLE KNOX CAPS ON FIRE DEPARTMENT | | | CONNECTION. | | | | | | PROVIDE PERMANENT WEATHERPROOF SIGNAGE FOR FIRE | | | DEPARTMENT CONNECTION. | | | | | | VERIFY TAMPER SWITCHES ARE SUPERVISING THE CONTROL | | | VALVES ON THE BACKFLOW PREVENTER. | | | | | | VERIFY EXISTING SPRINKLERS NOT BEING RELOCATED ARE | | | QUICK RESPONSE TYPE. | | | | | | REROUTE EXISTING FOUR INCH CROSS MAIN TO AVOID STAIR | | | ENTRY AND EXIT PENETRATIONS. | | | | | | A CEILING HEIGHT OF 14 FEET CORRESPONDS TO A HYDRAULIC | | | AREA OF AT LEAST 990 SQUARE FEET. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | | | | |
|