Plan Review Notes
Plan Review Notes For Permit 11030085
Permit Number 11030085
Review Stop B
Sequence Number 1
Notes
Date Text
2011-03-07 13:52:45****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. FBC R TABLE 302.1, 3' SEPARATION BETWEEN STRUCTURES
 AND 3' SEPARATION BETWEEN OVERHANG REQUIRED IF
 STRUCTURE HAS NO FIRE RESISTANCE. REVISE PLAN AS
 FOLLOWS:
  
 SHOW OVERHANG ON EXISTING HOUSE
 REVISE SITE PLAN TO SHOW MINIMUM SEPARATION (3' FROM
 OVERHANG) BETWEEN HOUSE AND EACH OF THE PROPOSED SHEDS,
 OR PROVIDE FIRE RESISTANCE AND OPENING INFORMATION TO
 COMPLY WITH FBC R TABLE 302.1
 SHOW DISTANCE BETWEEN THE TWO SHEDS (MINIMUM 3' WITH NO
 OVERHANG)
  
  
  