| Plan Review Notes For Permit 11030085 |
| Permit Number |
11030085 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-03-07 13:52:45 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. FBC R TABLE 302.1, 3' SEPARATION BETWEEN STRUCTURES | | | AND 3' SEPARATION BETWEEN OVERHANG REQUIRED IF | | | STRUCTURE HAS NO FIRE RESISTANCE. REVISE PLAN AS | | | FOLLOWS: | | | | | | SHOW OVERHANG ON EXISTING HOUSE | | | REVISE SITE PLAN TO SHOW MINIMUM SEPARATION (3' FROM | | | OVERHANG) BETWEEN HOUSE AND EACH OF THE PROPOSED SHEDS, | | | OR PROVIDE FIRE RESISTANCE AND OPENING INFORMATION TO | | | COMPLY WITH FBC R TABLE 302.1 | | | SHOW DISTANCE BETWEEN THE TWO SHEDS (MINIMUM 3' WITH NO | | | OVERHANG) | | | | | | | | | |
|