| Plan Review Notes For Permit 11030057 |
| Permit Number |
11030057 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-03-22 15:48:10 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PROVIDE A PLAN SHOWING PROPOSED WORK. | | | | | | 2. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB. | | | | | | 3. SEE HISTORIC APPROVAL, RENTAL LICENSE REQUIRED PRIOR | | | TO SUBMITTAL FOR BUILDING PERMIT. | | | | | | 4. . IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R | | | 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS | | | ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE | | | (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITYOFWPB.COM | | | /CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF) | | | | | | 5. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, | | | SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING | | | CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR | | | BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING | | | CANNOT BE REDUCED BY MORE THAN 5%. | | | | | | 6. APPLICATION INCLUDES "ELECTRICAL WORK" IN SCOPE BUT | | | NO ELECTRIC PLANS SUBMITTED. EITHER REMOVE FROM THE | | | APPLICATION OR PROVIDE ELECTRIC PLANS FOR REVIEW. | | | | | | | | | |
|