| 2011-03-02 14:51:25 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. PERMIT #06120381 WAS FOR REMOVING METAL SIDING, |
| | STUCCO EXTERIOR, INSTALL FOUR WINDOWS. PLEASE UPDATE |
| | VALUE TO INCLUDE ALL WORK IF THIS IS TO ADDRESS THE |
| | EXPIRED PERMIT APPLICATION AND WORK DONE WITHOUT |
| | PERMITS. |
| | |
| | 2. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, |
| | SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING |
| | CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR |
| | BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING |
| | CANNOT BE REDUCED BY MORE THAN 5%. |
| | |
| | 3. . IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R |
| | 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS |
| | ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE |
| | (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITYOFWPB.COM |
| | /CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF) |
| | |
| | 4. IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 606.4, |
| | PROVIDE CALCULATIONS. |
| | |
| | 5. PROVIDE THE TOTAL SQUARE FOOT AREA OF STUCCO |
| | INSTALLATION. PLEASE NOTE THAT THIS SHOULD INCLUDE THE |
| | ENTIRE HOUSE AS THAT WAS THE SCOPE OF WORK UNDER |
| | 06120381. |
| | |
| | 6. PLEASE NOTE THAT THE APPLICATION SUBMITTED IS FOR A |
| | FINAL INSPECTION. SHEATHING, VAPOR BARRIER, LATH, AND |
| | WINDOW BUCK INSPECTIONS ARE ALSO REQUIRED. THE |
| | INTEGRITY OF THE SUBSTRATE FOR THE STUCCO WILL BE |
| | REQUIRED TO BE VERIFIED AT INSPECTION. REPAIRS TO THE |
| | FRAMING MAY BE REQUIRED. THIS COMMENT IS ADVISORY ONLY |
| | (PERMIT WILL BE ISSUED WITH PROVISO). |
| | |
| | |