| 2011-03-15 10:15:39 | 2100 NORTH FLORIDA MANGO ROAD |
| | PERMIT #11030040 |
| | MASTER #10080396 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | |
| | PROVIDE SPRINKLER PROTECTION FOR EMERGENCY GENERATOR |
| | ROOM ATTACHED TO SOUTHWEST AREA OF BUILDING. |
| | |
| | TYCO EC-8 EXTENDED COVERAGE SPRINKLERS ARE NOT UL |
| | LISTED FOR ORDINARY HAZARD APPLICATIONS SUCH AS STORAGE |
| | ROOMS AND LOADING ZONE. REVISE HYDRAULIC CALCULATIONS. |
| | |
| | THE HYDRAULIC CALCULATION FOR THE EXTERIOR OVERHANG |
| | SHOULD INCLUDE ALL SPRINKLERS PROTECTING THIS SPACE. |
| | EXTENDED COVERAGE SPRINKLER NOT LISTED FOR ORDINARY |
| | HAZARD APPLICATIONS. REVISE CALCULATIONS. |
| | |
| | THE HYDRAULIC AREA FOR THE KITCHEN WAS CALCULATED |
| | PERPENDICULAR TO THE BRANCH LINES. NFPA 13 REQUIRES THE |
| | HYDRAULIC AREA TO BE MEASURED PARALLEL TO BRANCH LINES. |
| | REVISE CALCULATIONS. |
| | |
| | PROVIDE SPRINKLER COVERAGE BELOW OVERHEAD GARAGE DOORS |
| | IN STORAGE ROOM 19. |
| | |
| | PROVIDE LOCKABLE CAPS ON FIRE DEPARTMENT CONNECTION. |
| | PROVIDE WEATHERPROOF SIGNAGE FOR FIRE DEPARTMENT |
| | CONNECTION. |
| | |
| | PROVIDE CHAIN AND LOCK ON BACKFLOW PREVENTER. |
| | |
| | SPRINKLER DESIGN SHALL CONFORM TO THE 2002 EDITION OF |
| | NFPA 13. |
| | |
| | JOB VALUE ON PERMIT APPEARS TO BE UNDERVALUED AT 1.41 |
| | DOLLARS PER SQUARE FOOT. JOB VALUE SHALL INCLUDE TOTAL |
| | CONTRACT AMOUNT INCLUDING MATERIALS, LABOR AND |
| | OVERHEAD/PROFIT. PROVIDE A SIGNED COPY OF THE OFFICIAL |
| | CONTRACT. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |