2011-03-22 14:49:25****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE ENGINEERING FOR THE PROPOSED WALL, FS471,
 FBC R 301. RESISTANCE TO WIND LOADS HAS NOT BEEN
 DEMONSTRATED. CALCULATIONS MAY BE REQUIRED.
  
 2. WIND DESIGN CRITERIA SHOULD BE INCLUDED ON THE PLAN.
  
 3. SHOW THE FOOTER IN RELATION TO THE PROPERTY LINE.
 THE PROPOSED IMPROVEMENT CANNOT ENCROACH THE PROPERTY
 LINE.
  
 4. PLANS ARE TO BE ARCHITECTURAL QUALITY TO SCALE, FBC
 106. INCLUDE STRUCTURAL DETAIL FOR REBAR, ONE
 CONTINUOUS PIECE APPEARS TO BE SHOWN, FBC R 301.
  
  