Plan Review Notes
Plan Review Notes For Permit 11020699
Permit Number 11020699
Review Stop Z
Sequence Number 1
Notes
Date Text
2011-03-17 12:05:28PLANNING AND ZONING: **** FAILED ****
  
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 3. INDICATE SETBACK DIMENSIONS FROM PROPOSED EQUIPMENT
 TO ALL PROPERTY LINES ON SURVEY AND SITE PLAN. PURSUANT
 TO SECTION 94-305(B)(4) OF THE ZLDR: THE EQUIPMENT MAY
 NOT PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 THE MINIMUM SIDE SETBACK IS FIVE (5) FEET.
  
 4. PURSUANT TO SECTION 94-444(B) OPEN SPACE
 STANDARDS:
  
 (B) OUTDOOR STORAGE OF FUEL OR OIL OR PROPANE TANKS,
 ETC. SHALL NOT BE PERMITTED UNLESS APPROPRIATE
 SCREENING IS PROVIDED. SCREENING SHALL BE CONSTRUCTED
 OF BRICK, DECORATIVE CONCRETE, OTHER
 DECORATIVE MASONRY, OR COMPARABLY, DURABLE WOOD AND
 STEEL. THE HEIGHT OF THE AND ALUMINUM EXHAUST STACK IS
 10 FEET. THE SIX (6) FOOT FENCE WILL NOT SCREEN THE
 ENTIRE EQUIPMENT.
  
 FENCE SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES
 PLANTED AT TWO-FOOT INTERVALS. A FOUR-SIDED ENCLOSURE
 WITH MASONRY, OR COMPARABLY DURABLE WOOD AND STEEL, AN
 OBSCURING GATE IS REQUIRED AS A CONDITION FOR SITE PLAN
 APPROVAL.
  
 THE SCREENING SHALL ENCLOSE BOTH TANK AND EXHAUST STACK
 EQUIPMENT.
  
 PROVIDE A CROSS SECTION SHOWING THE EXISTING FENCE
 (NORTH AND SOUTH), EQUIPMENT AND LANDSCAPING.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  