Plan Review Notes
Plan Review Notes For Permit 11020678
Permit Number 11020678
Review Stop B
Sequence Number 2
Notes
Date Text
2011-03-02 09:48:16RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- ACCORDING TO PERMIT APPLICATION REPAIRS ARE 30% OF
 THE ENTIRE ROOF. 30% OF ROOF AREA IS NOT ALLOWED BY
 SEC. 611.1.1 OF 2007 FLORIDA BUILDING CODE-EXISTING
 BUILDING CODE. NEED TO RE-ROOF ENTIRE ROOF.
  
 2- ADJUST VALUATION TO INCLUDE TOTAL RE-ROOF. SEC.
 108.3 CITY AMENDMENTS TO FBC.
  
 3- ACCORDING TO MIAMI-DADE WEBSITE NOA 09-0331.10
 SUBMITTED FOR THE CONCRETE ROOF TILE WAS SUPERSEDED.
 VISIT MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA.
  
 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  