| Plan Review Notes For Permit 11020678 |
| Permit Number |
11020678 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-03-02 09:48:16 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- ACCORDING TO PERMIT APPLICATION REPAIRS ARE 30% OF | | | THE ENTIRE ROOF. 30% OF ROOF AREA IS NOT ALLOWED BY | | | SEC. 611.1.1 OF 2007 FLORIDA BUILDING CODE-EXISTING | | | BUILDING CODE. NEED TO RE-ROOF ENTIRE ROOF. | | | | | | 2- ADJUST VALUATION TO INCLUDE TOTAL RE-ROOF. SEC. | | | 108.3 CITY AMENDMENTS TO FBC. | | | | | | 3- ACCORDING TO MIAMI-DADE WEBSITE NOA 09-0331.10 | | | SUBMITTED FOR THE CONCRETE ROOF TILE WAS SUPERSEDED. | | | VISIT MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA. | | | | | | 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 | | | FLORIDA STATUTE. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | | | | |
|