| Plan Review Notes For Permit 11020670 |
| Permit Number |
11020670 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-02-25 16:02:09 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY AND | | | FASTENING OPTION IS GOING TO BE USED TO VERIFY | | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF | | | 2007 FLORIDA RESIDENTIAL CODE. | | | | | | 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | 07-1219.09 SUBMITTED. | | | ***NOTE: DESIGN PROFESSIONAL DOING THE RAS 117 | | | CALCULATIONS TO TAKE INTO CONSIDERATION THAT ACCORDING | | | TO 2009 REVISIONS SEC. R301.2.1.4.3 THIS BUILDING IS | | | LOCATED ON EXPOSURE "C". | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|