2011-02-25 16:02:09RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY AND
 FASTENING OPTION IS GOING TO BE USED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF
 2007 FLORIDA RESIDENTIAL CODE.
  
 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 07-1219.09 SUBMITTED.
 ***NOTE: DESIGN PROFESSIONAL DOING THE RAS 117
 CALCULATIONS TO TAKE INTO CONSIDERATION THAT ACCORDING
 TO 2009 REVISIONS SEC. R301.2.1.4.3 THIS BUILDING IS
 LOCATED ON EXPOSURE "C".
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712