2011-03-02 16:29:06****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. INSTALLATION SCHEDULE STATES THAT SHUTTERS WILL BE
 INSTALLED HORIZONTALLY, CONCRETE SUBSTRATE. THIS SHOULD
 BE BLOCK SUBSTRATE UNLESS THERE IS EVIDENCE THAT THERE
 ARE FORMED AND POURED COLUMNS AT EACH OPENING (RATHER
 THAN FILLED CELLS). PLEASE REVISE INSTALLATION SCHEDULE
 OR ADVISE AS TO HOW THIS INFORMATION HAS BEEN OBTAINED.
  
 2. SPAN DOES NOT CORRELATE WITH HORIZONTAL
 INSTALLATION, PLEASE ADDRESS.
  
  