| Plan Review Notes For Permit 11020628 |
| Permit Number |
11020628 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-02-07 13:44:26 | 201 SOUTH TAMARIND AVENUE | | | PERMIT #11020628 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****PROVISO***** PER THE FEBRUARY 28, 2012 LETTER FROM | | | MR. JEFFREY HALVERSON (WPB SENIOR PROJECT ENGINEER), | | | THE BUILDING AND COMBUSTIBLE EXTERIOR OVERHANGS WILL BE | | | FULLY SPRINKLERED BY JUNE 30, 2013. | | | | | | REVIEW COMMENT: FIRE DEPARTMENT ACCESS ROADS SHALL BE | | | PROVIDED SUCH THAT ANY PORTION OF THE BUILDING IS | | | LOCATED NOT MORE THAN 150 FEET FROM FIRE DEPARTMENT | | | ACCESS ROADS AS MEASURED BY AN APPROVED ROUTE AROUND | | | THE EXTERIOR OF THE BUILDING PER SECTION 18.2.3.2.2 OF | | | NFPA 1 FLORIDA 2007 EDITION. THE ACCESS DISTANCE CAN BE | | | INCREASED TO 450 FEET WHEN THE BUILDING IS FULLY | | | PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM. CURRENTLY | | | THE BUILDING IS ONLY PARTIALLY PROTECTED BY SPRINKLERS. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | |
|