Plan Review Notes
Plan Review Notes For Permit 11020628
Permit Number 11020628
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-03-25 11:43:43201 SOUTH TAMARIND AVENUE
 PERMIT #11020628
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 THE ADDRESS LISTED ON THE PERMIT APPLICATION INDICATES
 NORTH TAMARIND NOT SOUTH TAMARIND.
  
 FIRE DEPARTMENT ACCESS ROADS SHALL BE PROVIDED SUCH
 THAT ANY PORTION OF THE BUILDING IS LOCATED NOT MORE
 THAN 150 FEET FROM FIRE DEPARTMENT ACCESS ROADS AS
 MEASURED BY AN APPROVED ROUTE AROUND THE EXTERIOR OF
 THE BUILDING PER SECTION 18.2.3.2.2 OF NFPA 1 FLORIDA
 2007 EDITION. THE ACCESS DISTANCE CAN BE INCREASED TO
 450 FEET WHEN THE BUILDING IS FULLY PROTECTED BY AN
 AUTOMATIC SPRINKLER SYSTEM. CURRENTLY THE BUILDING IS
 ONLY PARTIALLY PROTECTED BY SPRINKLERS. NOTE: THE
 NEAREST FIRE HYDRANT IS ON THE EAST SIDE OF TAMARIND
 AVENUE.
  
 THE FIRE DEPARTMENT CONNECTION IS CURRENTLY LOCATED AT
 THE MIDPOINT OF THE EXISTING TRAIN STATION BUILDING ON
 THE EAST SIDE WHERE THE PROPOSED NEW DROP OFF AREA IS
 LOCATED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW