Plan Review Notes
Plan Review Notes For Permit 11020626
Permit Number 11020626
Review Stop P
Sequence Number 1
Notes
Date Text
2011-03-07 14:31:52FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 1) SHEET A1.1 PLEASE PROVIDE ADDITIONAL INFORMATION AS
 TO USAGE FOR HAND SINK LABELED #2. AT THIS TIME IT CAN
 NOT BE DETERMINED IF THIS SINK SHOULD ALSO BE TIED INTO
 THE GREASE INTERCEPTOR, 2007 FBC-P 1003.3.
  
 2) SHEET A1.1 ITEM MARKED NUMBER (8) A ICE MAKER IS NOT
 LOCATED ON SHEET P1 EITHER THE PLUMBING WATER PLAN NOR
 THE PLUMBING SANITARY PLAN.
  
 2A) THE ICE MACHINE MISSING ON THE PLUMBING SANITARY
 AND RISER PLAN WILL NEED TO SHOW COMPLIANCE WITH
 SECTION: 2007 FBC-P 802.1.1. PLEASE PROVIDE FLOOR SINK
 OR HUB DRAIN FOR COMPLIANCE.
  
 3) SHEET P-1 PLUMBING SANITARY PLAN INDICATES THE USE
 OF A ZURN- 2700-10, 20# GREASE TRAP WITH A 10 GPM FLOW.
 PLEASE PROVIDE CALCULATIONS FOR THIS UNIT FOR THE THREE
 COMPARTMENT SINK AND POSSIBLE #2 HAND SINK, 2007 FBC-P
 1003.4.1, 1003.3.4.2 & TABLE 1003.3.4.1. IT APPEARS TO
 BE TOO SMALL A UNIT. FOR EXAMPLE A STANDARD THREE
 COMPARTMENT SINK FLOWS AT 67.3 GAL PER MINUTE AT TWO
 MINUTES TO DRAIN. THAT WOULD REQUIRE A GREASE TRAP
 RATED AT 33.7 GPM.
  
 4) SHEET A1.1 PLEASE PROVIDE THE MINIMUM NUMBER OF
 REQUIRED PLUMBING FIXTURES PER 2007 FBC-P TABLE 403.1
 FOR THIS FLOOR WITH THE NEW TENANT SPACE ADDED SINCE
 THERE ARE NO PLUMBING FIXTURES LOCATED WITH THE TENANT
 SPACE.
 2007 FBC-P 403.2. WHERE PLUMBING FIXTURES ARE REQUIRED,
 SEPARATE FACILITIES SHALL BE PROVIDED FOR EACH SEX.
  
 ****NOTE****
 315.1 REQUIREMENTS. PUBLIC FOOD SERVICE ESTABLISHMENTS
 AND FOOD ESTABLISHMENTS, AS
 DEFINED IN CHAPTER 381 FLORIDA STATUTES, CHAPTER 500
 FLORIDA STATUTES AND CHAPTER 509
 FLORIDA STATUTES, SHALL COMPLY WITH THE APPLICABLE CODE
 REQUIREMENTS FOUND IN THE FLORIDA
 BUILDING CODE, BUILDING, CHAPTER 4, SPECIAL DETAILED
 REQUIREMENTS BASED ON USE AND
 OCCUPANCY.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  