| 2011-03-07 14:31:52 | FBC PLUMBING 2007 REVIEW #1 |
| | DENIED: |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | 1) SHEET A1.1 PLEASE PROVIDE ADDITIONAL INFORMATION AS |
| | TO USAGE FOR HAND SINK LABELED #2. AT THIS TIME IT CAN |
| | NOT BE DETERMINED IF THIS SINK SHOULD ALSO BE TIED INTO |
| | THE GREASE INTERCEPTOR, 2007 FBC-P 1003.3. |
| | |
| | 2) SHEET A1.1 ITEM MARKED NUMBER (8) A ICE MAKER IS NOT |
| | LOCATED ON SHEET P1 EITHER THE PLUMBING WATER PLAN NOR |
| | THE PLUMBING SANITARY PLAN. |
| | |
| | 2A) THE ICE MACHINE MISSING ON THE PLUMBING SANITARY |
| | AND RISER PLAN WILL NEED TO SHOW COMPLIANCE WITH |
| | SECTION: 2007 FBC-P 802.1.1. PLEASE PROVIDE FLOOR SINK |
| | OR HUB DRAIN FOR COMPLIANCE. |
| | |
| | 3) SHEET P-1 PLUMBING SANITARY PLAN INDICATES THE USE |
| | OF A ZURN- 2700-10, 20# GREASE TRAP WITH A 10 GPM FLOW. |
| | PLEASE PROVIDE CALCULATIONS FOR THIS UNIT FOR THE THREE |
| | COMPARTMENT SINK AND POSSIBLE #2 HAND SINK, 2007 FBC-P |
| | 1003.4.1, 1003.3.4.2 & TABLE 1003.3.4.1. IT APPEARS TO |
| | BE TOO SMALL A UNIT. FOR EXAMPLE A STANDARD THREE |
| | COMPARTMENT SINK FLOWS AT 67.3 GAL PER MINUTE AT TWO |
| | MINUTES TO DRAIN. THAT WOULD REQUIRE A GREASE TRAP |
| | RATED AT 33.7 GPM. |
| | |
| | 4) SHEET A1.1 PLEASE PROVIDE THE MINIMUM NUMBER OF |
| | REQUIRED PLUMBING FIXTURES PER 2007 FBC-P TABLE 403.1 |
| | FOR THIS FLOOR WITH THE NEW TENANT SPACE ADDED SINCE |
| | THERE ARE NO PLUMBING FIXTURES LOCATED WITH THE TENANT |
| | SPACE. |
| | 2007 FBC-P 403.2. WHERE PLUMBING FIXTURES ARE REQUIRED, |
| | SEPARATE FACILITIES SHALL BE PROVIDED FOR EACH SEX. |
| | |
| | ****NOTE**** |
| | 315.1 REQUIREMENTS. PUBLIC FOOD SERVICE ESTABLISHMENTS |
| | AND FOOD ESTABLISHMENTS, AS |
| | DEFINED IN CHAPTER 381 FLORIDA STATUTES, CHAPTER 500 |
| | FLORIDA STATUTES AND CHAPTER 509 |
| | FLORIDA STATUTES, SHALL COMPLY WITH THE APPLICABLE CODE |
| | REQUIREMENTS FOUND IN THE FLORIDA |
| | BUILDING CODE, BUILDING, CHAPTER 4, SPECIAL DETAILED |
| | REQUIREMENTS BASED ON USE AND |
| | OCCUPANCY. |
| | |
| | REVIEW BY LARRY WAGNER |
| | CHIEF PLUMBING INSPECTOR |
| | (561) 805-6692 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |
| | |
| | |