| 2011-04-04 15:43:38 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY PLUMBING | | | | | | 1) THE WATER VELOCITY SPECIFIED FOR THE FEATURE PUMP IS | | | INCORRECT. THE RETURN LINE SIZE IS LISTED AS 1.5 INCHES | | | AND THE FLOW IS 80 GPM. THIS PRODUCES A WATER VELOCITY | | | OF 12.59 FEET PER SECOND NOT 2.4. FBC R4101.6.3 LIMITS | | | THE VELOCITY TO 10 FEET PER SECOND FOR PRESSURE PIPING. | | | PLEASE CORRECT. | | | | | | 2) THE WATER VELOCITY IN THE 2 INCH SPA DRAIN TRUNK IS | | | GIVEN AS 8.2 FEET/SECOND. THE MAXIMUM VELOCITY ALLOWED | | | BY THE CODE IS 8 FEET/SECOND. PLEASE CORRECT. | | | | | | 3) THE WATER VELOCITY SPECIFIED FOR THE SPA PUMP IS | | | INCORRECT. THE RETURN LINE SIZE IS LISTED AS 2 INCH AND | | | THE FLOW IS 90 GPM. THIS PRODUCES A WATER VELOCITY OF | | | 9.2 FEET PER SECOND NOT 1.5. PLEASE CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|