Plan Review Notes
Plan Review Notes For Permit 11020607
Permit Number 11020607
Review Stop P
Sequence Number 2
Notes
Date Text
2011-03-22 15:14:572007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) SUBMIT 2 COPIES OF TOTAL DYNAMIC HEAD (TDH)
 CALCULATIONS FOR EACH OF THE SYSTEMS OR DESIGN THE
 SYSTEM FOR THE MAXIMUM FLOW RATE OF THE PUMP. THE
 REVISED PLANS SPECIFY A TDH OF 30FT FOR THE 1 HP
 FEATURE PUMP SYSTEM AND 56 FT FOR THE 1.5 HP PUMP
 SYSTEM. SUBMIT SIGNED AND SEALED CALCULATIONS SHOWING
 HOW THESE TWO TDH WERE DETERMINED. THERE WERE NO
 CALCULATIONS SUBMITTED INDICATING HOW THE TOTAL DYNAMIC
 HEAD FOR EACH OF THE SYSTEMS WAS DETERMINED. UNLESS THE
 TDH CALCULATIONS ARE SUBMITTED THE MAXIMUM CAPACITY OF
 THE PUMPS WILL BE USED TO DETERMINE THE WATER VELOCITY
 IN THE PIPES.
  
 2) ANSI/APSP-7 2006 SECTION 4.4 LIMITS THE WATER
 VELOCITY IN BRANCH SUCTION PIPING TO A MAXIMUM OF 6
 FEET PER SECOND WHEN ONE OF A PAIR IS BLOCKED. THE
 TABLES ON SHEET 3 OF THE REVISED DRAWINGS LIST THE FLOW
 AND VELOCITY WITH BOTH BRANCHES UNBLOCKED. HOWEVER, THE
 WATER VELOCITY IS LESS THAN 6 AT THE FLOW RATES/GPM
 SPECIFIED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]