2011-03-10 13:46:262007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) THE PLANS SPECIFY A 1.5 HP JANDY STEALTH SERIES
 VARIABLE SPEED PUMP WHICH REQUIRES THE MAXIMUM FLOW
 RATE OF THE PUMP TO BE USED IN CALCULATIONS. THE PIPING
 SCHEMATIC SHOWS 2.5" PIPE ON THE SPA SUCTION LINES AND
 THE MAIN DRAIN DETAIL SPECIFIES 2.5 " BRANCH PIPING
 BETWEEN THE TWO MAIN DRAINS. PLEASE CLARIFY. THE SPA
 MAIN DRAIN BRANCH PIPING BETWEEN THE TWO MAIN DRAINS IS
 LIMITED TO A MAXIMUM OF 6 FEET PER SECOND WHEN ONE OF
 THE PAIR IS BLOCKED PER ANSI/APSP-7. MAXIMUM OUTLET
 SIZE ON THE MANUFACTURED MAIN DRAIN SUMPS IS TYPICALLY
 2-1/2" AND IS CONSIDERED PART OF THE MAIN DRAIN BRANCH
 PIPING PER DEFINITION 3.5 OF ANSI/APSP-7 2006.
 THEREFORE, THE MAXIMUM BRANCH PIPING SIZE IS 2-1/2".
 UNLESS TDH CALCULATIONS ARE SUBMITTED THE MAXIMUM FLOW
 RATE OF THE PUMP WILL BE USED TO DETERMINE THE WATER
 VELOCITY. PLEASE SHOW HOW THE POOL PIPING WILL COMPLY
 WITH ANSI/APSP-7 SECTION 4.4 AND FBC R4101.6.3.
  
 2) THE SIZE OF THE BRANCH PIPING AT THE TWO SIDE DRAINS
 FOR THE SHEER DESCENT FEATURE IS NOT SPECIFIED. PROVIDE
 THE PUMP SPECS. WITH THE PUMP CURVE AND TDH
 CALCULATIONS TO SHOW COMPLIANCE FOR THIS SYSTEM AS
 WELL.
  
 3) SUBMIT 2 COPIES OF THE SPECIFICATIONS FOR THE POOL
 PUMP INCLUDING THE PUMP CURVE.
  
 4) SUBMIT 2 COPIES OF TOTAL DYNAMIC HEAD (TDH)
 CALCULATIONS FOR THE SYSTEM OR DESIGN THE SYSTEM FOR
 THE MAXIMUM FLOW RATE OF THE PUMP.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]