Plan Review Notes
Plan Review Notes For Permit 11020540
Permit Number 11020540
Review Stop B
Sequence Number 1
Notes
Date Text
2011-02-23 16:18:472007 FBC W/2009 REVISIONS
 RE-ROOF
  
 1) THE BUR SYSTEM THAT WAS SELECTED FROM NOA #
 08-0729.07 HAS A MAXIMUM DESIGN PRESSURE OF -60 PSF
 WHICH IS TOO LOW AT THE CORNER AND PERIMETER AREAS FOR
 A WIND SPEED OF 140 MPH IN EXPOSURE C. GENERAL
 LIMITATION #9 DOES IS SPECIFIED FOR THIS SYSTEM AND
 DOES NOT ALLOW ENHANCED FASTENING FOR INCREASING
 UPLIFT. PLEASE SELECT AN APPROPRIATE SYSTEM.
  
 2) LIMITATION #7 ALLOWS ENHANCED FASTENING WITH RAS 117
 CALCULATIONS FROM A FLORIDA REGISTERED ARCHITECT,
 ENGINEER OR REGISTERED ROOF CONSULTANT.
  
 3) IF THE BUR IS BEING INSTALLED ON AN INSULATED DECK
 SELECT THE APPROPRIATE SYSTEM FROM THE NOA.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]