| Plan Review Notes For Permit 11020498 |
| Permit Number |
11020498 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-03-08 12:09:13 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. ACCESSIBLE ROUTE CANNOT INCLUDE A STAIR, FBC | | | 11-4.1.2, 11-4.3.8 "AN ACCESSIBLE ROUTE DOESN OT | | | INCLUDE STAIRS, STEPS, OR ESCALATORS." | | | | | | 2. A LANDING IS REQUIRED AT THE TOP OF A STAIR, | | | FBC1009.4. IT APPEARS THAT THE DOOR ENCROACHES ON THE | | | STAIR LANDING. PLEASE PROVIDE DIMENSIONS TO SHOW | | | COMPLIANCE. | | | | | | 3. SEE FBC 1012.8 REGARDING HANDRAILS WITHIN 30" FOR | | | STAIRS. | | | | | | 4. FBC 1003.5.2, THIS APPEARS TO BE A PART OF THE EXIT | | | DISCHARGE. SEE FBC 1002, EXIT DISCHARGE, "THAT PORTION | | | OF A MEANS OF EGRESS SYSTEM BETWEEN THE TERMINATION OF | | | AN EXIT AND THE PUBLIC WAY." SEE FBC1003.5.2; IF THIS | | | IS A PART OF THE EXIT DISCHARGE, A RAMP IS REQUIRED. | | | | | | IT IS NOTED THAT EXISTING CONDITIONS DO NOT COMPLY WITH | | | SOME OF THE REQUIREMENTS OF THE FBC AND THAT THERE MAY | | | BE DESIGN CONSTRAINTS DUE TO EXISTING CONDITIONS | | | (TECHNICAL INFEASIBILITY). PLEASE FEEL FREE TO CONTACT | | | ME IF YOU WISH TO DISCUSS THIS MATTER. | | | | | | | | | | | | | | | |
|