| Plan Review Notes For Permit 11020458 |
| Permit Number |
11020458 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-03-07 13:12:13 | 1700 PALM BEACH LAKES BOULEVARD - 10TH FLOOR | | | PERMIT #11020458 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | AS NOTED ON THE DRAWINGS, SEPARATE PLANS AND PERMIT | | | REQUIRED FOR MODIFICATIONS TO FIRE SPRINKLER SYSTEM AND | | | FIRE ALARM SYSTEM. | | | | | | FIRE ALARM VISUAL NOTIFCATION APPLIANCES REQUIRED | | | WITHIN FIFTEEN FEET FROM THE END OF A CORRIDOR. | | | | | | FIRE ALARM VISUAL NOTIFICATION APPLIANCES REQUIRED IN | | | CONFERENCE ROOM 142 & 143, TRAINING ROOM 126, AND | | | RESTROOMS 147 & 149. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|