| Plan Review Notes For Permit 11020351 |
| Permit Number |
11020351 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-02-15 11:23:56 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO | | | BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN | | | PRESSURES OF SEC. R301 OF 2007 FLORIDA RESIDENTIAL | | | CODE. | | | | | | 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | SUBMITTED. | | | ***NOTE: ASSEMBLIES WITH GENERAL LIMITATION #9 CAN'T BE | | | USED IN THIS BUILDING BECAUSE GENERAL LIMITATION #9 | | | DOESN'T ALLOW NAIL ENHANCING. | | | | | | 3- NOA 08-0227.09 SUBMITTED WAS SUPERSEDED BY | | | MIAMI-DADE WEBSITE. NEED TO SUBMIT CURRENT NOA | | | 08-0410.09. | | | | | | 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW. SEC. 108.3 CITY AMENDMENTS TO FBC. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|