Plan Review Notes
Plan Review Notes For Permit 11020351
Permit Number 11020351
Review Stop B
Sequence Number 1
Notes
Date Text
2011-02-15 11:23:56RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF 2007 FLORIDA RESIDENTIAL
 CODE.
  
 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED.
 ***NOTE: ASSEMBLIES WITH GENERAL LIMITATION #9 CAN'T BE
 USED IN THIS BUILDING BECAUSE GENERAL LIMITATION #9
 DOESN'T ALLOW NAIL ENHANCING.
  
 3- NOA 08-0227.09 SUBMITTED WAS SUPERSEDED BY
 MIAMI-DADE WEBSITE. NEED TO SUBMIT CURRENT NOA
 08-0410.09.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 108.3 CITY AMENDMENTS TO FBC.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712