| Plan Review Notes For Permit 11020341 |
| Permit Number |
11020341 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-02-22 08:34:32 | DESCRIPTION OF WORK IS INCOMPLETE AND INADEQUATELY | | | DETAILED. PLEASE PROVIDE ADDITIONAL INFORMATION. | | | | | | INDICATE THE SIZE OF THE EXISTING SERVICE. NEC 230.31 | | | SPECIFY THE TYPE OF CONDUIT TO BE UTILIZED. NEC 110.8 | | | INDICATE THE SIZE AND TYPE OF NEW SERVICE FEEDERS. NEC | | | 310.8, 310.16 | | | PROVIDE A PLAN SHOWING HOW THE NEW SERVICE WILL BE | | | SUPPORTED. NEC 110.13 | | | SPECIFY THE ENCLOSURE TYPE (OUTDOOR USAGE) REQUIRED FOR | | | THE SERVICE. NEC 110.20 | | | PROVIDE CLARIFICATION AS TO THE LOCATION AND REQUIRED | | | ACCESS TO THE MAIN ELECTRIC DISCONNECT. NEC 230.70 | | | SHOW HOW THE NEW SERVICE WILL BE GROUNDED. NEC 250.20, | | | 250.32 (A) AND (B), TABLE 250.66 | | | PROVIDE AN INTERSYSTEM BONDING BAR AT THE SERVICE. NEC | | | 250.94 | | | | | | NOTE: THE NEW LOCATION OF THIS SERVICE WILL REQUIRE | | | ZONING REVIEW AND APPROVAL. | | | | | | ROBERT LECKY, ELECTRICAL PLAN REVIEW, 561-805-6718 | | | |
|