2011-02-16 09:48:28RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW SECOND
 CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
  
 ENGINEERING CALCULATIONS SUBMITTED:
  
 1- DESIGN PRESSURES SHOWN BY THE ENGINEER FOR ROOF
 ZONES 1, 2 AND 3 DON'T CORRESPOND TO EXPOSURE "C".
 REVISE AS REQUIRED.
  
 2- PROVIDE ACTUAL RAS 117 CALCULATIONS TO VERIFY
 COMPLIANCE WITH RAS 117. CALCULATIONS WERE NOT
 SUBMITTED.
  
 3- ENGINEER TO IDENTIFY WHICH SPECIFIC APPROVED
 ASSEMBLY FROM NOA 08-0410.09 SUBMITTED IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES REQUIRED BY SEC. R301 OF 2007 FLORIDA
 RESIDENTIAL CODE AND PROPOSED NAIL ENHANCING.
  
 4- ENGINEER'S LETTER REFERS TO POLYGLASS NOA. NOA
 SUBMITTED IS FOR CERTAIN TEED CORPORATION NOT
 POLYGLASS. REVISE AS REQUIRED.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712