| Plan Review Notes For Permit 11020330 |
| Permit Number |
11020330 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-02-16 09:48:28 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW SECOND | | | CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | | | | ENGINEERING CALCULATIONS SUBMITTED: | | | | | | 1- DESIGN PRESSURES SHOWN BY THE ENGINEER FOR ROOF | | | ZONES 1, 2 AND 3 DON'T CORRESPOND TO EXPOSURE "C". | | | REVISE AS REQUIRED. | | | | | | 2- PROVIDE ACTUAL RAS 117 CALCULATIONS TO VERIFY | | | COMPLIANCE WITH RAS 117. CALCULATIONS WERE NOT | | | SUBMITTED. | | | | | | 3- ENGINEER TO IDENTIFY WHICH SPECIFIC APPROVED | | | ASSEMBLY FROM NOA 08-0410.09 SUBMITTED IS GOING TO BE | | | INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN | | | PRESSURES REQUIRED BY SEC. R301 OF 2007 FLORIDA | | | RESIDENTIAL CODE AND PROPOSED NAIL ENHANCING. | | | | | | 4- ENGINEER'S LETTER REFERS TO POLYGLASS NOA. NOA | | | SUBMITTED IS FOR CERTAIN TEED CORPORATION NOT | | | POLYGLASS. REVISE AS REQUIRED. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|