2011-02-14 13:42:37RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- SPECIFY WHICH APPROVED ASSEMBLY FROM NOA 08-0410.09
 SUBMITTED IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC. R301 OF 2007 FLORIDA
 RESIDENTIAL CODE.
  
 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED.
  
 ***NOTES: A)DESIGN PROFESSIONAL DOING THE RAS 117
 CALCULATIONS TO TAKE INTO CONSIDERATION THAT ACCORDING
 TO 2009 REVISIONS SEC. R301.2.1.4.3 OF 2007 FLORIDA
 RESIDENTIAL CODE THIS BUILDING IS LOCATED ON EXPOSURE
 "C".
  
 B) ASSEMBLIES THAT ARE LIMITED BY GENERAL LIMITATION #9
 CAN'T BE USED IN THIS AREA BECAUSE THEY DON'T MEET THE
 DESIGN PRESSURES AND NAIL ENHANCING IS NOT ALLOWED. SEE
 GENERAL LIMITATION #9 ON LAST PAGE OF NOA.
  