1 |
|
| Notes |
| Date |
Text |
| 2011-02-17 11:11:55 | 10130 NORTHLAKE BOULEVARD, SUITE #110 | | | PERMIT #11020317 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS | | | OF NFPA 241. | | | | | | DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION | | | CODE 2007 EDITION: NFPA 1 AND NFPA 101 - 2006 EDITION | | | WITH FLORIDA AMENDMENTS. | | | | | | ALL STORAGE TO BE LOCATED AT LEAST 24-INCHES BELOW THE | | | CEILING. | | | | | | STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS | | | CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO | | | THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS | | | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED | | | REFLECTIVE COLOR AND BEAR THE LETTER R PER FLORIDA | | | STATUTE 633.027 AND FLORIDA ADMINISTRATIVE CODE | | | 69A-60.0081. | | | | | | PROVIDE BUILDING SUITE ADDRESS ON THE BUILDING. NUMBERS | | | SHALL BE AT LEAST THREE-INCHES IN HEIGHT AND SHALL | | | CONTRAST THE BACKGROUND. | | | | | | PROVIDE AN ADDITIONAL EXIT SIGN IN THE LARGE PEDICURE | | | ROOM TO INDICATE AN EXIT DOOR EXISTS AT THE REAR OF THE | | | BUILDING. | | | | | | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | | SYSTEM AND FIRE ALARM SYSTEM. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|