| 2011-02-28 09:57:46 | 2007 FBC W/2009 |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) SUBMIT A COPY OF THE PAID RECEIPT FOR THE COUNTY |
| | IMPACT FEES. |
| | |
| | 2) THE FLORIDA PRODUCT APPROVAL COVERSHEETS FOR THE |
| | WINDOWS, MULLIONS AND DOORS ARE FOR THE 2004 CODE |
| | VERSION. SUBMIT THE ONES FOR THE 2007 CODE VERSION. |
| | |
| | 3) THE FLORIDA PRODUCT APPROVAL COVERSHEET FOR THE DOOR |
| | IS FROM A DIFFERENT MANUFACTURER (BENCHMARK) THAN THE |
| | ATTACHED MIAMI-DADE NOA (JELD-WEN). THE FILE STATUS IS |
| | CLOSED FOR THE NOA NO. 07-0731.04. SUBMIT CURRENT |
| | PRODUCT APPROVAL THAT HAS BEEN REVIEWED AND APPROVED BY |
| | THE DESIGNER OF RECORD. |
| | |
| | 4) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE FIXED |
| | GLASS WINDOW IN THE NEW BEDROOM. |
| | |
| | 5) THE ENERGY CALCULATION FORM THAT WAS SUBMITTED |
| | REQUIRES CEILINGS TO BE INSULATED TO A MINIMUM OF R-30. |
| | THE PLANS SPECIFY R-19 INSULATION IN THE CEILINGS AND |
| | THE FORM HAS R-19. IN ORDER TO USE THIS METHOD EACH |
| | COMPONENT IS REQUIRED TO MEET OR EXCEED THE PERFORMANCE |
| | CRITERIA ON THE FORM, OTHERWISE METHOD A MUST BE USED. |
| | PLEASE CORRECT. |
| | |
| | 6) THE OWNER/AGENT IS REQUIRE TO SIGN THE ENERGY |
| | CALCULATION FORMS. |
| | |
| | 7) SHOW COMPLIANCE WITH FBC R703.6.3 FOR THE REQUIRED |
| | BOND BREAK BETWEEN THE WATER-RESISTIVE BARRIER AND THE |
| | EXTERIOR STUCCO. |
| | |
| | 8) SHOW COMPLIANCE WITH FBC R703.6.2 AND ASTM C 1063 |
| | FOR THE FOUNDATION WEEP SCREED AT THE BOTTOM OF ALL |
| | FRAMED EXTERIOR WALLS BELOW THE FLOOR LINE WHERE THE |
| | WALL IS SUPPORTED BY A FLOOR OR FOUNDATION. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |