| Plan Review Notes For Permit 11020297 |
| Permit Number |
11020297 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-02-15 14:35:53 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PLEASE PROVIDE MORE INFORMATION AS TO HOW YOU HAVE | | | DETERMINED THAT THE BOTTOM SUBSTRATE IS CONCRETE RATHER | | | THAN FILLED CMU. ALTERNATIVELY, PLEASE REVISE | | | INSTALLATION SCHEDULE FOR BLOCK ON THE BOTTOM. | | | | | | 2. PLEASE EXPLAIN SPANS; HOW CAN SPAN BE THE SAME SIZE | | | AS OPENING WITH A 2.5 INCH EDGE DISTANCE, WALL MOUNT? | | | PLEASE REVISE INSTALLATION SCHEDULE. | | | | | | 3. SEE OPENING 2, ANCHOR SPACING DOES NOT COMPLY WITH | | | CHART IN PRODUCT APPROVAL FOR THIS SPAN AND CONNECTION | | | TYPE. PLEASE REVISE AND CHECK ALL OPENINGS. | | | |
|