| Plan Review Notes For Permit 11020296 |
| Permit Number |
11020296 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-02-15 12:44:12 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. HOW HAS IT BEEN DETERMINED THAT SUBSTRATE, BOTTOM, | | | IS CONCRETE RATHER THAN FILLED CMU? THIS CONFLICTS WITH | | | OUR RECORDS. PLEASE ADDRESS BY EITHER REVISING | | | INSTALLATION SCHEDULE OR PROVIDE MORE INFORMATION. | | | | | | 2. ON THE PRODUCT APPROVLA, CIRCLE DETAILS USED FOR THE | | | ARMOR SCREEN. I WAS UNABLE TO LOCATE 2.5" EDGE | | | DISTANCE, 191" SPAN, 12" ANCHOR SPACING. | | | | | | 3. INSTALLATION SCHEDULE SPECIFIES TAPCONS FOR ARMOR | | | SCREEN. THIS FASTENER IS NOT ONE WHICH IS AN OPTION IN | | | THE PRODUCT APPROVAL. SUBMIT EITHER SITE SPECIFIC | | | ENGINEERING OR REVISE. | | | | | | 4. WHEN RESUBMITTING, DO NOT HIGHLIGHT THE INSTALLATION | | | SCHEDULE AS IT IS DIFFICULT TO READ AND CANNOT BE | | | PROPERLY SCANNED. | | | | | | 5. SPAN IS NOT CLEAR. WITH A 2.5" EDGE DISTANCE, SPAN | | | SHOULD NOT BE THE SAME AS OPENING SIZE. PLEASE REVISE. | | | | | | 6. PROVIDE ROOM DESIGNATION FOR THE EMERGENCY MEANS OF | | | ESCAPE. | | | | | | |
|