| Date |
Text |
| 2011-03-01 16:58:44 | 2007 FBC W/2009 REVISIONS |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) SUBMIT TWO COPIES OF A SOIL TEST AS REQUIRED BY FBC |
| | R401.4 FROM A FLORIDA LICENSED GEO-TECHNICAL ENGINEER. |
| | |
| | 2) PROVIDE TWO COPIES OF A SURFACE WATER DRAINAGE PLAN |
| | TO SHOW COMPLIANCE WITH FBC R401.3. |
| | |
| | 3) SHOW COMPLIANCE WITH FBC R309.2 FOR GARAGE |
| | SEPARATION FROM THE RESIDENCE AND HABITABLE ROOMS |
| | ABOVE. |
| | |
| | 4) SHOW COMPLIANCE WITH FBC R502.1.2 FOR DRAFT-STOPPING |
| | FLOOR/CEILING ASSEMBLIES INTO AREAS OF CONCEALED SPACES |
| | NOT EXCEEDING 1000 SQFT. |
| | |
| | 5) SPECIFY THE TRUSS TO WALL CONNECTORS FOR THE UPPER |
| | AND LOWER ROOFS. |
| | |
| | 6) THE WALL SECTION ON SHEET 3 SPECIFIES A SIMPSON H-14 |
| | ANCHOR WHICH IS A TRUSS TO WOOD CONNECTOR. THE EXTERIOR |
| | WALLS ARE MASONRY AT THE FIRST AND SECOND FLOORS. |
| | PLEASE CORRECT. |
| | |
| | 7) PROVIDE AN ANCHOR/STRAPPING DETAIL FOR THE WOOD |
| | FRAMED CHIMNEY. |
| | |
| | 8) THE ENERGY CALCULATIONS AND THE ELECTRICAL PANEL |
| | SCHEDULE APPEAR TO INDICATE TWO TANKLESS ELECTRIC WATER |
| | HEATERS. THE ARCHITECTURAL PLANS DO NOT SPECIFY |
| | TANKLESS WATER HEATERS. PLEASE CLARIFY. |
| | |
| | 9) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR THE |
| | WINDOWS AND DOORS ON THE PLANS. THE WORSE CASE IS THE |
| | 30" OCTAGON WINDOWS LOCATED IN WALL ZONE 5 WITH |
| | TRIBUTARY AREAS OF LESS THAN 10 SQUARE FEET WITH 140 |
| | MPH WIND-SPEED IN EXPOSURE C WITH A MEAN ROOF HEIGHT OF |
| | 25 FEET. |
| | |
| | 10) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| | SPECIFICATIONS AND LISTINGS FOR THE GAS FIREPLACE AND |
| | FLUE. |
| | |
| | 11) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 12) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE |
| | OVERHEAD GARAGE DOOR THAT WILL BE INSTALLED. |
| | |
| | 13) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED |
| | TO INSTALL THE ROOF TILE AND PROVIDE ADEQUATE |
| | RESISTANCE TO OVERTURNING MOMENT. IF ADHESIVE OR FOAM |
| | IS USED, SUBMIT THE APPROPRIATE PRODUCT APPROVALS. |
| | |
| | 14) SUBMIT PRODUCT APPROVALS FOR THE OUT-SWING ENTRY |
| | DOOR WITH A SIDELITE AS SHOWN ON THE PLANS. |
| | |
| | 15) SUBMIT PRODUCT APPROVALS FOR THE OUT-SWING GARAGE |
| | DOOR. |
| | |
| | 16) PRODUCT APPROVALS WERE SUBMITTED FOR A HORIZONTAL |
| | SLIDING WINDOW. THERE ARE NO WINDOWS OF THIS TYPE ARE |
| | SHOWN ON THE PLANS. PLEASE CLARIFY. |
| | |
| | 17) SUBMIT AN INSTALLATION SCHEDULE FOR THE STORM |
| | PANELS THAT WILL BE INSTALLED ON THE NON-IMPACT RATED |
| | DOOR. SPECIFY THE MOUNT TYPE, THE SPAN, THE GLASS |
| | SEPARATION, THE ANCHOR TYPE, ANCHOR SPACING, EDGE |
| | DISTANCE AND WALL SUBSTRATE. |
| | |