| | BUILDING PLAN REVIEW |
| | PERMIT:11020243 |
| | ADD: 500 N CONGRESS AVE. BLDG# C |
| | CONT: PAUL DAVIS RESTORATION |
| | TEL: (561)248-7167 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | |
| | |
| | |
| | |
| | BUILDING PROVISO: |
| | |
| | SHEET A-4-0 DETAILS 4 & 5. FIRE BLOCKING 717.2.3 FIRE |
| | BLOCKING CONNECTIONS BETWEEN HORIZONTAL AND VERTICAL |
| | SPACES. |
| | |
| | DRAFTSTOPPING IN FLOORS: |
| | 717.3.2 GROUPS R-1, R-2, R-3 AND R-4. DRAFTSTOPPING |
| | SHALL BE PROVIDED IN FLOOR/CEILING SPACES IN GROUP R-1 |
| | BUILDINGS, IN GROUP R-2 BUILDINGS WITH THREE OR MORE |
| | DWELLING UNITS, IN GROUP R-3 BUILDINGS WITH TWO |
| | DWELLING UNITS AND IN GROUP R-4 BUILDINGS. |
| | DRAFTSTOPPING SHALL BE LOCATED ABOVE AND IN LINE WITH |
| | THE DWELLING UNIT AND SLEEPING UNIT SEPARATIONS. |
| | |
| | DRAFTSTOPPING IN ATTICS: |
| | 717.4.2 GROUPS R-1 AND R-2. DRAFTSTOPPING SHALL BE |
| | PROVIDED IN ATTICS, MANSARDS, OVERHANGS OR OTHER |
| | CONCEALED ROOF SPACES OF GROUP R-2 BUILDINGS WITH THREE |
| | OR MORE DWELLING UNITS AND IN ALL GROUP R-1 BUILDINGS. |
| | DRAFTSTOPPING SHALL BE INSTALLED ABOVE, AND IN LINE |
| | WITH, SLEEPING UNIT AND DWELLING UNIT SEPARATION WALLS |
| | THAT DO NOT EXTEND TO THE UNDERSIDE OF THE ROOF |
| | SHEATHING ABOVE. EXCEPTIONS: |
| | 3.IN OCCUPANCIES IN GROUP R-2 THAT DO NOT EXCEED FOUR |
| | STORIES IN HEIGHT, THE ATTIC SPACE SHALL BE SUBDIVIDED |
| | BY DRAFTSTOPS INTO AREAS NOT EXCEEDING 3,000 SQUARE |
| | FEET (279 M2) OR ABOVE EVERY TWO DWELLING UNITS, |
| | WHICHEVER IS SMALLER. |
| | |
| | SHEET A-1.1 UNIT #23 GENERAL NOTE #3, RENOVATION KEY |
| | NOTE # 14 BOTH INDICATE THAT NEW WINDOWS WILL BE |
| | INSTALLED AT UNIT # 23. THE MIAMI-DADE PRODUCT APPROVAL |
| | SUBMITTED 06-1211.07 IS A NON-IMPACT WINDOW THAT WILL |
| | REQUIRE WINDOW PROTECTION, STORM SHUTTERS UNDER A |
| | SEPARATE PERMIT, REVIEW AND FEES. |
| | |
| | |
| | JAMES A. WITMER C.B.O. |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: (561)805-6715 |
| | FAX:(561)805-6731 |