| Plan Review Notes For Permit 11020189 |
| Permit Number |
11020189 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-02-14 10:07:05 | 250 SOUTH AUSTRALIAN AVENUE, 8TH FLOOR | | | PERMIT NUMBER 11020189 | | | NEW ACCESS CONTROL EQUIPMENT | | | | | | 1. WRONG EDITION OF NFPA 101, THE LIFE SAFETY CODE | | | REFERENCED. SHOULD READ 2006 EDITION NOT THE 2003 | | | EDITION. THE 2006 EDITION OF 7.2.1.6.2 HAS EIGHT (8) | | | INFORMATION SECTIONS NOT SEVEN (7) AS ILLUSTRATED ON | | | SHEET A-1.0. PLEASE REVISE PLANS. | | | | | | 2. THE EXISTING CARD READERS DISPLAYED ON SHEET A-1.0 | | | IN THE EXISTING EXIT STAIR AND EXISTING EXIT STAIR | | | VESTIBULE CANNOT BE ONE OF THE ASSIGNED RE-ENTRY POINTS | | | FOR THE BUILDING. PLEASE SEE NFPA 101, SECTION | | | 7.2.1.5.7 AND 7.2.1.5.7.1. | | | | | | 3. THE INSTALLATION OF SECURITY DEVICES CANNOT | | | INTERFERE WITH ANY EXITING. | | | | | | 4. A STICKER ON THE PLAN INDICATES THE INSTALLATION OF | | | ONE CARD READER HOWEVER THE PLANS INDICATES THE | | | INSTALLATION OF AT LEAST TWO NEW CARD READERS. | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|