Plan Review Notes
Plan Review Notes For Permit 11020189
Permit Number 11020189
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-02-14 10:07:05250 SOUTH AUSTRALIAN AVENUE, 8TH FLOOR
 PERMIT NUMBER 11020189
 NEW ACCESS CONTROL EQUIPMENT
  
 1. WRONG EDITION OF NFPA 101, THE LIFE SAFETY CODE
 REFERENCED. SHOULD READ 2006 EDITION NOT THE 2003
 EDITION. THE 2006 EDITION OF 7.2.1.6.2 HAS EIGHT (8)
 INFORMATION SECTIONS NOT SEVEN (7) AS ILLUSTRATED ON
 SHEET A-1.0. PLEASE REVISE PLANS.
  
 2. THE EXISTING CARD READERS DISPLAYED ON SHEET A-1.0
 IN THE EXISTING EXIT STAIR AND EXISTING EXIT STAIR
 VESTIBULE CANNOT BE ONE OF THE ASSIGNED RE-ENTRY POINTS
 FOR THE BUILDING. PLEASE SEE NFPA 101, SECTION
 7.2.1.5.7 AND 7.2.1.5.7.1.
  
 3. THE INSTALLATION OF SECURITY DEVICES CANNOT
 INTERFERE WITH ANY EXITING.
  
 4. A STICKER ON THE PLAN INDICATES THE INSTALLATION OF
 ONE CARD READER HOWEVER THE PLANS INDICATES THE
 INSTALLATION OF AT LEAST TWO NEW CARD READERS.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION