| 2011-03-04 15:51:04 | 250 SOUTH AUSTRALIAN AVENUE SUITE #1700 | | | PERMIT #11020187 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****PROVISO***** | | | | | | REMOVE ACCESS CONTROLLED EGRESS DEVICE (CARD READER) | | | FROM BOTH STAIR EXITS BECAUSE THE 17TH FLOOR IS A | | | DESIGNATED RE-ENTRY FLOOR THAT MUST ALLOW OCCUPANTS | | | RE-ENTRY AT ALL TIMES. | | | | | | WESLEY JOLIN/MIKE CARSILLO | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|