| Plan Review Notes For Permit 11020187 |
| Permit Number |
11020187 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-02-14 11:23:57 | 250 AUSTRALIAN AVENUE, 17TH FLOOR | | | PERMIT NUMBER 11020187 | | | ACCESS CONTROL EQUIPMENT | | | | | | | | | 1. WRONG NFPA 101, LIFE SAFETY CODE REFERENCED. SHOULD | | | READ 2006 EDITION INSTEAD OF 2003 EDITION. THE 2006 | | | EDITION SECTION 7.2.1.6.2 HAS EIGHT (8) SECTIONS NOT | | | (7) SECTIONS. | | | | | | 2. A STICKER ON THE PLANS INDICATES THE INSTALLATION OF | | | THREE CARD READERS BUT THE PLANS INDICATES FIVE CARD | | | READERS. | | | | | | 3. THE EXISTING CARD READERS IN THE STAIRWELL AND THE | | | EXISTING STAIR VESTIBULE MAY IMPACT THE RE-ENTRY POINT | | | FROM THE STAIR. PLEASE SEE NFPA 101, THE LIFE SAFETY | | | CODE SECTIONS 7.2.1.5.7 AND 7.2.1.5.7. | | | | | | 4. SECURITY DEVICES INSTALLED CANNOT INTERFERE WITH | | | EXITING. | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|