2011-02-14 11:23:57250 AUSTRALIAN AVENUE, 17TH FLOOR
 PERMIT NUMBER 11020187
 ACCESS CONTROL EQUIPMENT
  
  
 1. WRONG NFPA 101, LIFE SAFETY CODE REFERENCED. SHOULD
 READ 2006 EDITION INSTEAD OF 2003 EDITION. THE 2006
 EDITION SECTION 7.2.1.6.2 HAS EIGHT (8) SECTIONS NOT
 (7) SECTIONS.
  
 2. A STICKER ON THE PLANS INDICATES THE INSTALLATION OF
 THREE CARD READERS BUT THE PLANS INDICATES FIVE CARD
 READERS.
  
 3. THE EXISTING CARD READERS IN THE STAIRWELL AND THE
 EXISTING STAIR VESTIBULE MAY IMPACT THE RE-ENTRY POINT
 FROM THE STAIR. PLEASE SEE NFPA 101, THE LIFE SAFETY
 CODE SECTIONS 7.2.1.5.7 AND 7.2.1.5.7.
  
 4. SECURITY DEVICES INSTALLED CANNOT INTERFERE WITH
 EXITING.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION