Plan Review Notes
Plan Review Notes For Permit 11020183
Permit Number 11020183
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-02-14 15:49:08250 AUSTRALIAN AVENUE, 18TH FLOOR
 PERMIT NUMBER 11020183
 ACCESS CONTROL EQUIPMENT
  
  
 1. WRONG LIFE SAFETY CODE REFERENCED. SHOULD READ NFPA
 101, THE LIFE SAFETY CODE, 2006 EDITION NOT THE 2003
 EDITION. THE 2006 EDITION HAS EIGHT BULLET POINTS FOR
 7.2.1.6.2 NOT THE SEVEN LISTED ON THE PLAN.
  
 2. SECURITY DEVICE INSTALLATION SHALL NOT INTERFERE
 WITH EXITING.
  
 3. THE STICKER ON THE PLANS DO NOT MATCH THE DRAWINGS
 INDICATING HOW MANY CARD READERS ARE PLANNED TO BE
 INSTALLED.
  
 4. THE EXITING CARD READERS IN THE EXIT STAIR AND THE
 EXISTING EXIT STAIR VESTIBULE MAY CREATE PROBLEMS IF
 THIS FLOOR IS BEING USED AS RE-ENTRY. PLEASE SEE NFPA
 101, SECTION 7.2.1.5.6 AND 7.2.1.5.7.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  
  