| Plan Review Notes For Permit 11020183 |
| Permit Number |
11020183 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-02-14 15:49:08 | 250 AUSTRALIAN AVENUE, 18TH FLOOR | | | PERMIT NUMBER 11020183 | | | ACCESS CONTROL EQUIPMENT | | | | | | | | | 1. WRONG LIFE SAFETY CODE REFERENCED. SHOULD READ NFPA | | | 101, THE LIFE SAFETY CODE, 2006 EDITION NOT THE 2003 | | | EDITION. THE 2006 EDITION HAS EIGHT BULLET POINTS FOR | | | 7.2.1.6.2 NOT THE SEVEN LISTED ON THE PLAN. | | | | | | 2. SECURITY DEVICE INSTALLATION SHALL NOT INTERFERE | | | WITH EXITING. | | | | | | 3. THE STICKER ON THE PLANS DO NOT MATCH THE DRAWINGS | | | INDICATING HOW MANY CARD READERS ARE PLANNED TO BE | | | INSTALLED. | | | | | | 4. THE EXITING CARD READERS IN THE EXIT STAIR AND THE | | | EXISTING EXIT STAIR VESTIBULE MAY CREATE PROBLEMS IF | | | THIS FLOOR IS BEING USED AS RE-ENTRY. PLEASE SEE NFPA | | | 101, SECTION 7.2.1.5.6 AND 7.2.1.5.7. | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | | | | |
|