| 2011-05-10 11:06:41 | DENIED BY BUILDING |
| | |
| | 1) SUBMIT 2 SETS OF PRODUCT APPROVALS FOR THE ROOF TILE |
| | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PER DCA RULE 9B-72 AND CITY |
| | AMENDMENTS 106.3.3. SPECIFY THE METHOD OF ATTACHMENT |
| | THAT WILL BE USED FROM THE OPTIONS PROVIDED IN THE |
| | PRODUCT APPROVALS, INSURING THAT THE SELECTED METHOD IS |
| | CAPABLE OF RESISTING THE OVERTURNING MOMENT FOR THE |
| | WINDSPEED AND EXPOSURE CATEGORY FOR THE STRUCTURE'S |
| | LOCATION. FBC R905.1 AND R905.3. |
| | |
| | 2) THE TRUSS LAYOUT FROM THE TRUSS MANUFACTURER IS NOT |
| | SIGNED AND SEALED BY THE TRUSS ENGINEER. THERE ARE |
| | STILL SOME TRUSS ANCHORS WITH INADEQUATE UPLIFT |
| | CAPACITIES ON THE ROOF FRAMING PLAN. THE ROOF FRAMING |
| | PLAN AND THE TRUSS LAYOUT DIFFER IN THE KITCHEN AREA. |
| | CHECK LOCATION OF GIRDER TRUSS D1G. THERE IS A CLOUDED |
| | NOTE ON THE ROOF FRAMING PLAN AT THE REAR OF THE |
| | STRUCTURE FOR GIRDER TRUSS M1G SPECIFYING DETAIL 5 ON |
| | A7. THIS GABLE END DETAIL DOES NOT APPLY AT THIS |
| | LOCATION. PLEASE CORRECT THE ROOF FRAMING PLAN. |
| | NOTE: THE TRUSS DRAWINGS AND TRUSS LAYOUT FROM THE |
| | TRUSS COMPANY FOR SINGLE FAMILY RESIDENTIAL |
| | CONSTRUCTION CAN BE SUBMITTED TO THE BUILDING INSPECTOR |
| | IN THE FIELD AT THE TIME OF INSPECTION. |
| | |
| | 3) BEFORE A PERMIT TO CONSTRUCT CAN BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION. 233-5025 |
| | |