| Plan Review Notes For Permit 11020180 |
| Permit Number |
11020180 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-03-09 11:43:04 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY MECHANICAL | | | | | | 1) THE MECHANICAL PLANS HAVE THE NAME AND LICENSE | | | NUMBER OF THE ARCHITECT IN THE TITLE BLOCK, BUT THE | | | PLANS HAVE NOT BEEN SIGNED AND SEALED BY HIM. FS 481. | | | FS 471.003 ALLOWS A MECHANICAL CONTRACTOR TO DESIGN | | | SYSTEMS NOT TO EXCEED 15-TONS. IF HVAC SYSTEM IS | | | DESIGNED BY THE MECHANICAL CONTRACTOR THE CONTRACTOR'S | | | SIGNATURE AND LICENSE NUMBER IS REQUIRED ON THE PLAN. | | | | | | 2) ON PAGE 4 OF THE EQUIPMENT SIZING CALCULATIONS THE | | | TOTAL CALCULATED LOAD IS SPECIFIED AS 17,831 BTU (1.7 | | | TONS) AND THE EQUIPMENT IS SPECIFIED AS 25,200 BTU (2.5 | | | TONS). IT APPEARS THAT A 2 TON UNIT WOULD BE REQUIRED. | | | SECTION 1107.AB.1.1 OF THE REVISED ENERGY CODE STATES | | | THAT COOLING EQUIPMENT SHALL BE SELECTED SO THAT ITS | | | TOTAL CAPACITY IS NOT LESS THAN THE CALCULATED LOAD BUT | | | NOT MORE THAN 1.15 TIMES GREATER THAN THE TOTAL | | | CALCULATED LOAD. | | | | | | 3) THE ENERGY FORMS SPECIFY EQUIPMENT WITH SEER 14 AND | | | THE PLANS LISTS THE EQUIPMENT AS SEER 13. PLEASE | | | CORRECT. | | | | | | 4) SPECIFY THE CFM AT EACH OF THE SUPPLY OUTLETS ON THE | | | PLANS. | | | | | | 5) THE MECHANICAL PLANS SPECIFY THREE HVAC SYSTEMS AND | | | THE REST OF THE PLANS ONLY HAVE TWO. PLEASE COORDINATE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|