Plan Review Notes
Plan Review Notes For Permit 11020180
Permit Number 11020180
Review Stop M
Sequence Number 1
Notes
Date Text
2011-03-09 11:43:042007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) THE MECHANICAL PLANS HAVE THE NAME AND LICENSE
 NUMBER OF THE ARCHITECT IN THE TITLE BLOCK, BUT THE
 PLANS HAVE NOT BEEN SIGNED AND SEALED BY HIM. FS 481.
 FS 471.003 ALLOWS A MECHANICAL CONTRACTOR TO DESIGN
 SYSTEMS NOT TO EXCEED 15-TONS. IF HVAC SYSTEM IS
 DESIGNED BY THE MECHANICAL CONTRACTOR THE CONTRACTOR'S
 SIGNATURE AND LICENSE NUMBER IS REQUIRED ON THE PLAN.
  
 2) ON PAGE 4 OF THE EQUIPMENT SIZING CALCULATIONS THE
 TOTAL CALCULATED LOAD IS SPECIFIED AS 17,831 BTU (1.7
 TONS) AND THE EQUIPMENT IS SPECIFIED AS 25,200 BTU (2.5
 TONS). IT APPEARS THAT A 2 TON UNIT WOULD BE REQUIRED.
 SECTION 1107.AB.1.1 OF THE REVISED ENERGY CODE STATES
 THAT COOLING EQUIPMENT SHALL BE SELECTED SO THAT ITS
 TOTAL CAPACITY IS NOT LESS THAN THE CALCULATED LOAD BUT
 NOT MORE THAN 1.15 TIMES GREATER THAN THE TOTAL
 CALCULATED LOAD.
  
 3) THE ENERGY FORMS SPECIFY EQUIPMENT WITH SEER 14 AND
 THE PLANS LISTS THE EQUIPMENT AS SEER 13. PLEASE
 CORRECT.
  
 4) SPECIFY THE CFM AT EACH OF THE SUPPLY OUTLETS ON THE
 PLANS.
  
 5) THE MECHANICAL PLANS SPECIFY THREE HVAC SYSTEMS AND
 THE REST OF THE PLANS ONLY HAVE TWO. PLEASE COORDINATE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]