2011-03-11 15:47:48PLANS REDLINED:
 PROVIDE AN INTER SYSTEM BONDING STRIP AT ELECTRIC
 SERVICE. NEC 250.94
 A GFCI PROTECTED RECEPTACLE IS REQUIRED TO SERVE AC CU
 #2. NEC 210.63
 AHU #3 MISSING FROM PANEL SCHEDULE
  
 ROBERT LECKY, ELECTRICAL PLANS REVIEW, 561-805-6718
  
  