| 2011-03-07 15:47:37 | 2007 FBC W/2009 REVISIONS |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C AND |
| | THE PLANS WERE DESIGNED FOR EXPOSURE CATEGORY B. THE |
| | COMPONENT AND CLADDING PRESSURES WILL NEED TO BE |
| | INCREASED AS WELL AS THE UPLIFTS FOR THE ROOF TRUSSES. |
| | PLEASE CORRECT. |
| | |
| | 2) SUBMIT TWO COPIES OF THE SPECS. AND LISTING |
| | INFORMATION FOR THE GAS BBQ AND THE VENT-LESS GAS |
| | FIREPLACE. |
| | |
| | 3) IN ADDITION TO THE BUILDING PAD DENSITY TEST THAT |
| | WAS SUBMITTED, PLEASE SUBMIT TWO COPIES OF A |
| | GEOTECHNICAL REPORT TO VERIFY THE SAFE BEARING CAPACITY |
| | OF THE SOIL. FBC R401.4 |
| | |
| | 4) THE MECHANICAL PLANS SPECIFY THREE HVAC SYSTEMS. THE |
| | ARCHITECTURAL PLANS AND ELECTRICAL PLANS SPECIFY TWO |
| | SYSTEMS. PLEASE COORDINATE THE PLANS. |
| | |
| | 5) THE MECHANICAL PLANS SHOW THE THIRD A/C CONDENSING |
| | UNIT LOCATED WHERE POOL HEATER WILL BE LOCATED. PLEASE |
| | CLARIFY. |
| | |
| | 7) SUBMIT TWO SETS OF TRUSS LAYOUT DRAWINGS THAT HAVE |
| | BEEN SIGNED AND SEALED BY THE TRUSS ENGINEER AND |
| | REVIEWED AND APPROVED BY THE DESIGNER OF RECORD FOR THE |
| | STRUCTURE. |
| | |
| | 8) THE ROOF TRUSSES HAVE BEEN DESIGNED FOR 140 MPH WIND |
| | SPEED AND EXPOSURE CATEGORY C. HOWEVER, THE ROOF |
| | FRAMING PLANS NEED TO BE REVISED TO REFLECT THE |
| | INCREASED UPLIFTS FOR EXPOSURE C. SOME OF THE SPECIFIED |
| | TRUSS ANCHORS ARE NOT ADEQUATE. |
| | |
| | 9) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 10) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE |
| | EXTERIOR DOUBLE ENTRY DOORS, THE SINGLE OUT-SWING |
| | DOORS, THE LARGE AND SMALL OVERHEAD GARAGE DOORS AND |
| | THE STRUCTURAL WINDOW MULLIONS AS REQUIRED BY DCA RULE |
| | 9B-72. |
| | |
| | 11) ON SHEET A8.0 STEEL HEADER DETAIL #35 IS SPECIFIED |
| | FOR A WIND PRESSURE OF 35 PSF. IS THIS CORRECT? WHERE |
| | IS IT TO BE INSTALLED? |
| | |
| | 12) SPECIFY THE METHOD OF ATTACHMENT AND MINIMUM |
| | ATTACHMENT RESISTANCE THAT WILL BE USED TO INSTALL THE |
| | ROOF TILE. |
| | |
| | 13) BEFORE A PERMIT TO CONSTRUCT CAN BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION. 233-5025 |
| | |