2011-03-07 15:47:372007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C AND
 THE PLANS WERE DESIGNED FOR EXPOSURE CATEGORY B. THE
 COMPONENT AND CLADDING PRESSURES WILL NEED TO BE
 INCREASED AS WELL AS THE UPLIFTS FOR THE ROOF TRUSSES.
 PLEASE CORRECT.
  
 2) SUBMIT TWO COPIES OF THE SPECS. AND LISTING
 INFORMATION FOR THE GAS BBQ AND THE VENT-LESS GAS
 FIREPLACE.
  
 3) IN ADDITION TO THE BUILDING PAD DENSITY TEST THAT
 WAS SUBMITTED, PLEASE SUBMIT TWO COPIES OF A
 GEOTECHNICAL REPORT TO VERIFY THE SAFE BEARING CAPACITY
 OF THE SOIL. FBC R401.4
  
 4) THE MECHANICAL PLANS SPECIFY THREE HVAC SYSTEMS. THE
 ARCHITECTURAL PLANS AND ELECTRICAL PLANS SPECIFY TWO
 SYSTEMS. PLEASE COORDINATE THE PLANS.
  
 5) THE MECHANICAL PLANS SHOW THE THIRD A/C CONDENSING
 UNIT LOCATED WHERE POOL HEATER WILL BE LOCATED. PLEASE
 CLARIFY.
  
 7) SUBMIT TWO SETS OF TRUSS LAYOUT DRAWINGS THAT HAVE
 BEEN SIGNED AND SEALED BY THE TRUSS ENGINEER AND
 REVIEWED AND APPROVED BY THE DESIGNER OF RECORD FOR THE
 STRUCTURE.
  
 8) THE ROOF TRUSSES HAVE BEEN DESIGNED FOR 140 MPH WIND
 SPEED AND EXPOSURE CATEGORY C. HOWEVER, THE ROOF
 FRAMING PLANS NEED TO BE REVISED TO REFLECT THE
 INCREASED UPLIFTS FOR EXPOSURE C. SOME OF THE SPECIFIED
 TRUSS ANCHORS ARE NOT ADEQUATE.
  
 9) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 10) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE
 EXTERIOR DOUBLE ENTRY DOORS, THE SINGLE OUT-SWING
 DOORS, THE LARGE AND SMALL OVERHEAD GARAGE DOORS AND
 THE STRUCTURAL WINDOW MULLIONS AS REQUIRED BY DCA RULE
 9B-72.
  
 11) ON SHEET A8.0 STEEL HEADER DETAIL #35 IS SPECIFIED
 FOR A WIND PRESSURE OF 35 PSF. IS THIS CORRECT? WHERE
 IS IT TO BE INSTALLED?
  
 12) SPECIFY THE METHOD OF ATTACHMENT AND MINIMUM
 ATTACHMENT RESISTANCE THAT WILL BE USED TO INSTALL THE
 ROOF TILE.
  
 13) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION. 233-5025
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved