2011-03-23 09:07:41BUILDING PLAN REVIEW
 PERMIT: 11020155
 ADD: 111 EXECUTIVE CENTER BUILDING# 4 FLOORS 1-3
 CONT: WALKER CONTRACTING GROUP
 TEL: (239)289-4815
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 2007 EXISTING BUILDING CODE W/ 2009 SUPPLEMENTS
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) PLEASE COMPLY WITH 712.6 IF WORK IS ABOVE DROPPED
 ACOUSTICAL CEILING: 2007 FBC-B 712.6 FIRE WALLS, FIRE
 BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS AND SMOKE
 PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING IN A MANNER
 ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION. SUCH
 IDENTIFICATION SHALL BE ABOVE ANY DECORATIVE CEILING
 AND IN CONCEALED SPACES. SUGGESTED WORDING FOR FIRE AND
 SMOKE BARRIERS: "FIRE AND SMOKE BARRIER - PROTECT ALL
 OPENINGS."
  
 2) PROVIDE 1 HOUR UL LISTING ASSEMBLY OR EQUIVALENT FOR
 1 HOUR RATED CORIDOR BY TIME OF INSPECTION.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]