2011-02-28 09:22:54BUILDING PLAN REVIEW
 PERMIT: 11020155
 ADD: 111 EXECUTIVE CENTER BUILDING# 4 FLOORS 1-3
 CONT: WALKER CONTRACTING GROUP
 TEL: (239)289-4815
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 2007 EXISTING BUILDING CODE W/ 2009 SUPPLEMENTS
  
 1ST REVIEW
 ACTION: DENIED
 1) THE SUBMITTED PLAN IS A COPY, EITHER A SIGNMED AND
 SEALED ORIGINAL PLAN IS REQUIRED OR THE CONTRACTOR WILL
 NEED TO SUPPLY A PLAN THAT IS THEIR OWN DESIGN,
 CONTRACTOR OD RECORD WILL NEED TO SIGN AND PRINT THE
 QUALIFIERS NAME AND LICENSE NUMBER.
  
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS OR EXEMPTION
 FL ADMIN CODE 61G16.003 ARCHITECTS OR EXEMPTION
  
 2) THE DESIGNER OF RECORD WILL NEED TO PICK A
 COMPLIANCE METHOD 101.5 2007 FBC-EXISTING BUILDING
 CODE, IF THE WORK AREA COMPLIANCE METHOD IS PICKED
 (101.5.2) THEN A LEVEL OF ALTERATION WILL ALSO NEED TO
 BE INDICATED, 2007 FBC-EXISTING 401.4).
  
 3) THE PLANS FAIL TO INDICATE THE HEIGHT OF THE
 BUILDING AND IF THE BUILDING IS FIRE SPRINKLERED? IF
 THE SPRINKLERS CONFORM WITH 2007 FBC 903.3..1.1 OR
 903.3.1.2?
  
 4) THE PLANS DO NOT INDICATE THE OCCUPANCY BUT THE
 HEADER STRIP DOES INDICATE A RETIREMENT COMMUNITY, IS
 THIS A I-1 OR A R-2 OCCUPANCY?
 IN EITHER CASE 2007 FBC-B TABLE 1017.1REQUIRES THE
 CORRIDOR WALLS TO BE A 1 HOUR FIRE RATING, PLEASE
 PROVIDE A CUT SECTION OF WALL AND EITHER A UL LISTING
 OR GYPSUM NUMBER.
  
 5) THE PERMIT APPLICATION INDICATES THE RESIDENT ENETRY
 DOORS ARE TO BE REPLACED, PLEASE PROVIDE ADDITIONAL
 INFORMATION, 2007 FBC-B
 TABLE 715.4 OPENING PROTECTIVES, WILL THERE BE GLAZING
 WITHIN THE DOOR UNIT, IF SO HOW MANY SQUARE INCHES?
  
 6) THE PLANS FAIL TO INDICATE IF THE RATED CEILING OF
 THE CORRIDOR IS TO BE REPLACED? PLEASE REVIEW 2007
 FBC-BUILDING 438.3 HORIZONTAL SEPERATION SHALL BE
 CONSTRUCTED IN ACCORDANCE WITH 711.
  
 7) PLEASE ADD NOTE ON PLANS FOR COMPLIANCE WITH: 2007
 FBC-B 712.6 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS,
 SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
 REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE
 AND SMOKE BARRIER - PROTECT ALL OPENINGS."
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]