Plan Review Notes
Plan Review Notes For Permit 11020150
Permit Number 11020150
Review Stop P
Sequence Number 1
Notes
Date Text
2011-02-25 11:32:532007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) THE PLANS SPECIFY THREE DIFFERENT SIZE PUMPS. SHEET
 1 OF 4 LISTS A 1-1/2 HP UNDER POOL SPECIFICATIONS AND A
 SHARED 2.0 HP UNDER AUX POOL SPECS. SHEET 3 OF 4 LISTS
 A 1.0 HP INTELLIFLO PUMP. PLEASE CLARIFY.
  
 2) SUBMIT TWO COPIES OF THE POOL PUMP SPECIFICATIONS
 AND THE PUMP CURVE FOR THE PUMP THAT WILL BE INSTALLED.
  
 3) SUBMIT TWO COPIES OF TOTAL DYNAMIC HEAD
 CALCULATIONS. NOTE: IF TDH CALCULATIONS ARE NOT
 SUBMITTED THE WATER VELOCITY WILL BE DETERMINED USING
 THE MAXIMUM FLOW RATE OF THE PUMP. IF IT IS A VARIABLE
 SPEED PUMP THE MAXIMUM CAPACITY OF THE PUMP WILL BE
 USED.
  
 4) WHEN USING TWO MAIN DRAINS, ANSI/APSP 7 - 2006
 LIMITS THE WATER VELOCITY IN BRANCH SUCTION PIPING TO 6
 FEET PER SECOND WHEN ONE OF A PAIR BLOCKED. THEREFORE,
 THE TWO MAIN DRAIN OUTLETS AND THE PIPING BETWEEN THEM
 WILL NEED TO COMPLY. THE MAIN DRAIN DETAIL SPECIFIES 2"
 BRANCH PIPING.
  
 5) THE ATMOSPHERIC PRESSURE RELIEF VENT SHOWN ON THE
 MAIN DRAIN DETAIL IS NO LONGER ACCEPTED AS AN
 ANTI-ENTRAPMENT DEVICE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]