| Notes |
| Date |
Text |
| 2011-02-16 17:01:24 | 1665 PALM BEACH LAKES BOULEVARD, SUITE #100 | | | PERMIT #11020146 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE MINIMUM OF THREE-INCH HIGH NUMBERS INDICATING | | | SUITE NUMBER AT ENTRY. | | | | | | PROVIDE DOOR CLOSERS ON ALL FIRE RATED CORRIDOR DOORS. | | | | | | A THUMB TURN LATCH IS ONLY PERMITTED ON PRINCIPAL | | | ENTRANCE DOORS PER SECTION 39.2.2.2.2 IN THE LIFE | | | SAFETY CODE OF THE FLORIDA FIRE PREVENTION CODE. | | | PROVIDE AN OPEN/CLOSE LOCK STATUS WINDOW OR SIMILAR | | | ALLOWING OCCUPANTS TO READILY DETERMINE IF THE DOOR IS | | | LOCKED PER SECTION 7.2.1.5.4. | | | | | | VERIFY EXISTING DOOR EX2 HAS A 20 MINUTE FIRE RATING. | | | | | | DROP TEST ALL NEW MECHANICAL FIRE DAMPERS. | | | | | | PROVIDE SEPARATE PLANS AND PERMITS FOR ALL FIRE ALARM | | | AND FIRE SPRINKLER WORK. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | | | | |
|