2011-02-16 17:01:241665 PALM BEACH LAKES BOULEVARD, SUITE #100
 PERMIT #11020146
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE MINIMUM OF THREE-INCH HIGH NUMBERS INDICATING
 SUITE NUMBER AT ENTRY.
  
 PROVIDE DOOR CLOSERS ON ALL FIRE RATED CORRIDOR DOORS.
  
 A THUMB TURN LATCH IS ONLY PERMITTED ON PRINCIPAL
 ENTRANCE DOORS PER SECTION 39.2.2.2.2 IN THE LIFE
 SAFETY CODE OF THE FLORIDA FIRE PREVENTION CODE.
 PROVIDE AN OPEN/CLOSE LOCK STATUS WINDOW OR SIMILAR
 ALLOWING OCCUPANTS TO READILY DETERMINE IF THE DOOR IS
 LOCKED PER SECTION 7.2.1.5.4.
  
 VERIFY EXISTING DOOR EX2 HAS A 20 MINUTE FIRE RATING.
  
 DROP TEST ALL NEW MECHANICAL FIRE DAMPERS.
  
 PROVIDE SEPARATE PLANS AND PERMITS FOR ALL FIRE ALARM
 AND FIRE SPRINKLER WORK.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  
  