| 2011-03-11 11:38:50 | 2007 FBC W/2009 REVISIONS |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE |
| | EXTERIOR DOOR AND WINDOWS. IF THE WINDOWS ARE MULLED |
| | TOGETHER, SUBMIT TWO COPIES OF THE PRODUCT APPROVALS |
| | FOR THE STRUCTURAL MULLIONS. DCA RULE 9B-72 |
| | |
| | 2) PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY |
| | AMENDMENTS FBC 106.3.3 |
| | |
| | 3) SUBMIT TWO COPIES OF RAS 117 CALCULATIONS FOR |
| | ENHANCED FASTENING IN ORDER TO MEET THE HIGHER UPLIFT |
| | REQUIREMENTS AT THE CORNER AND PERIMETER AREAS OF THE |
| | ROOF AS REQUIRED BY LIMITATION #7 OF THE PRODUCT |
| | APPROVAL FOR THE TAMKO MODIFIED BITUMEN ROOF SYSTEM. |
| | |
| | 4) THE ENERGY CALCULATIONS THAT WERE SUBMITTED CONTAINS |
| | NUMEROUS ERRORS. THE FLOOR TYPE SHOWN ON THE PLANS IS A |
| | CRAWL SPACE NOT A SLAB, WHICH REQUIRES INSULATION. THE |
| | WALL TYPE ON PLANS IS 2 X 6 WOOD FRAME NOT CONCRETE |
| | BLOCK. THE CEILING TYPE FOR THE ADDITION SHOWN ON THE |
| | PLANS IS A SINGLE ASSEMBLY 2 X 8 FLAT ROOF NOT UNDER |
| | ATTIC. PLEASE CORRECT. |
| | |
| | 5) THE ENERGY FORM IS REQUIRED TO BE SIGNED BY THE |
| | OWNER/AGENT. PLEASE CORRECT. |
| | |
| | 6) THE ENERGY FORM INDICATES THAT THE CEILING FAN |
| | CREDIT IS BEING TAKEN. SUBMIT PLANS SHOWING THE |
| | LOCATIONS AND SIZES OF THE CEILING FANS AS REQUIRED BY |
| | SECTION C4.2.1.1 OF THE REVISED 2007 FLORIDA ENERGY |
| | GLITCH AMENDMENTS. |
| | |
| | 7) THE PLANS WILL REQUIRE REVIEW FOR IMPACT FEES. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |