Plan Review Notes
Plan Review Notes For Permit 11020129
Permit Number 11020129
Review Stop B
Sequence Number 2
Notes
Date Text
2011-03-11 11:38:502007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 EXTERIOR DOOR AND WINDOWS. IF THE WINDOWS ARE MULLED
 TOGETHER, SUBMIT TWO COPIES OF THE PRODUCT APPROVALS
 FOR THE STRUCTURAL MULLIONS. DCA RULE 9B-72
  
 2) PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS FBC 106.3.3
  
 3) SUBMIT TWO COPIES OF RAS 117 CALCULATIONS FOR
 ENHANCED FASTENING IN ORDER TO MEET THE HIGHER UPLIFT
 REQUIREMENTS AT THE CORNER AND PERIMETER AREAS OF THE
 ROOF AS REQUIRED BY LIMITATION #7 OF THE PRODUCT
 APPROVAL FOR THE TAMKO MODIFIED BITUMEN ROOF SYSTEM.
  
 4) THE ENERGY CALCULATIONS THAT WERE SUBMITTED CONTAINS
 NUMEROUS ERRORS. THE FLOOR TYPE SHOWN ON THE PLANS IS A
 CRAWL SPACE NOT A SLAB, WHICH REQUIRES INSULATION. THE
 WALL TYPE ON PLANS IS 2 X 6 WOOD FRAME NOT CONCRETE
 BLOCK. THE CEILING TYPE FOR THE ADDITION SHOWN ON THE
 PLANS IS A SINGLE ASSEMBLY 2 X 8 FLAT ROOF NOT UNDER
 ATTIC. PLEASE CORRECT.
  
 5) THE ENERGY FORM IS REQUIRED TO BE SIGNED BY THE
 OWNER/AGENT. PLEASE CORRECT.
  
 6) THE ENERGY FORM INDICATES THAT THE CEILING FAN
 CREDIT IS BEING TAKEN. SUBMIT PLANS SHOWING THE
 LOCATIONS AND SIZES OF THE CEILING FANS AS REQUIRED BY
 SECTION C4.2.1.1 OF THE REVISED 2007 FLORIDA ENERGY
 GLITCH AMENDMENTS.
  
 7) THE PLANS WILL REQUIRE REVIEW FOR IMPACT FEES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]