| 2011-02-16 16:29:19 | 2007 FBC W/2009 REVISIONS |
| | |
| | 1) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE |
| | EXTERIOR WINDOWS, DOOR, IMPACT PROTECTION DEVICES, ROOF |
| | COVERING MATERIAL AS REQUIRED BY DCA RULE 9B-72. THE |
| | PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | 2) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE |
| | ADDITION AS REQUIRED BY THE 2007 ENERGY GLITCH |
| | AMENDMENTS N1100.0.3. THE FORM IS REQUIRED TO BE SIGNED |
| | BY THE PREPARER AN THE OWNER/AGENT. |
| | |
| | 3) SPECIFY THE CEILING, WALL AND UNDER-FLOOR INSULATION |
| | THAT WILL BE INSTALLED. THE TYPICAL EXTERIOR WALL |
| | SECTION ON A-4 SHOWS A 2 X 4 FRAME WALL WITH R-30 |
| | INSULATION. PLEASE CORRECT. |
| | |
| | 4) SHOW COMPLIANCE WITH FBC R319.1(5) PROTECTION |
| | AGAINST DECAY FOR WOOD SHEATHING AND FRAMING WITHIN 6 |
| | INCHES OF THE GROUND. |
| | |
| | 5) SHOW COMPLIANCE WITH R320.1 FOR TERMITE PROTECTION. |
| | |
| | 6) SPECIFY THE ROOF OVERHANG AT THE ADDITION. IF IT IS |
| | LESS THAN 6 INCHES, GUTTERS ARE REQUIRED IN ACCORDANCE |
| | WITH R320.7. |
| | |
| | 7) SHOW COMPLIANCE WITH R408.2 FOR UNDER-FLOOR |
| | VENTILATION. |
| | |
| | 8) SHOW COMPLIANCE WITH R408.4 FOR UNDER-FLOOR SPACE |
| | ACCESS. |
| | |
| | 9) SHOW COMPLIANCE WITH R704.1 FOR THE REQUIRED BOND |
| | BREAK BETWEEN THE WATER-RESISTANT BARRIER AND THE |
| | STUCCO ON THE EXTERIOR WALLS. |
| | |
| | 10) SHOW COMPLIANCE WITH R704.1 FOR THE CLEARANCE |
| | BETWEEN THE EXTERIOR WALL COVERING AND THE FINAL EARTH |
| | GRADE OF NOT LESS THAN 6 INCHES FOR INSPECTION FOR |
| | TERMITE INFESTATION. |
| | |
| | 11) SHOW COMPLIANCE WITH R806.1 FOR VENTILATION |
| | REQUIRED FOR ENCLOSED RAFTER SPACES FORMED WHERE |
| | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| | RAFTERS. |
| | |
| | 12) FBC R905.11.1 REQUIRES MODIFIED BITUMEN MEMBRANE |
| | ROOFS TO HAVE A MINIMUM SLOPE OF 1/4" PER FOOT. THE |
| | PLANS SPECIFY 1/8" PER FOOT. PLEASE CORRECT. |
| | |
| | 13) SHOW COMPLIANCE WITH R313.2.1 FOR THE INSTALLATION |
| | OF SMOKE ALARMS. |
| | |