| Plan Review Notes For Permit 11020118 |
| Permit Number |
11020118 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-02-09 12:42:50 | SHOW RELATIVE LOCATION OF ELECTRICAL PANELS AND | | | DISCONNECTS. VERIFY MAIN SERVICE DISCONNECTS ARE | | | GROUPED IN ONE LOCATION. INDICATE LOCATION OF NEW | | | ELECTRICAL EQUIPMENT ON A FLOOR PLAN. NEC 230.71 | | | VERIFY THE EXISTING SERVICE AND ELECTRICAL EQUIPMENT | | | INTENDED TO INTERRUPT CURRENT AT FAULT LEVELS HAS A | | | SUFFICIENT INTERRUPTING RATING. PROVIDE SPECIFICATIONS | | | AND FAULT CURRENT INTERRUPTING RATING FOR PANELS AND | | | DISCONNECTS. NEC 110.9, 110.10 | | | PROVIDE SPECIFICATIONS ON THE NEW TRANSFORMER. | | | TRANSFORMERS OF MORE THAN 112 ?? KVA REQUIRE A FIRE | | | RESISTANT TRANSFORMER ROOM. NEC 450.21 | | | SECONDARY OVERCURRENT PROTECTION IS REQUIRED AT THE | | | TRANSFORMER. NEC 450.3, 240.21 ( C ) | | | HOW WILL THE TRANSFORMER BE PHYSICALLY PROTECTED? NEC | | | 450.8 | | | PROVIDE A LOAD CALCULATION FOR DETERMINING CONDUCTOR | | | SIZE AND OVERCURRENT PROTECTION ON THE PRIMARY AND | | | SECONDARY SIDE OF THE NEW TRANSFORMER. NEC 450-3(B) | | | NOTE: A SEPARATE ELECTRIC PERMIT AND PLAN IS REQUIRED | | | FOR ELECTRICAL CONNECTION OF THE NEW EQUIPMENT. | | | | | | ROBERT LECKY, ELECTRIC PLAN REVIEW, 561-805-6718 | | | |
|