| Plan Review Notes For Permit 11020061 |
| Permit Number |
11020061 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-03-02 12:39:55 | VERIFY THE AVAILABLE FAULT CURRENT IS LESS THAN 10,000 | | | AMPS. NEC 110.9 | | | PROVIDE AN INTER SYSTEM BONDING STRIP AT ELECTRIC | | | SERVICE. NEC 250.94 | | | 3/0 CONDUCTORS ARE REQUIRED FOR FEEDERS PROTECTED WITH | | | 200 AMPERE BREAKER. NEC T. 310.16 | | | PANEL ???A??? (POOL) REQUIRES A #3 FEEDER CONDUCTOR | | | WITH #8 GROUNDS. NEC T 310.16 | | | A GFCI PROTECTED RECEPTACLE IS REQUIRED TO SERVE CU #1 | | | AND #2. NEC 210.63 | | | SEVERAL RECEPTACLES REQUIRE LABELING FOR GFCI | | | PROTECTION. THESE ARE LOCATED ON THE WEST PORCH, EAST | | | PORCH AND KITCHENETTE. NEC 210.8 | | | ADDITIONAL RECEPTACLES ARE REQUIRED IN THE FAMILY ROOM, | | | KITCHEN ALCOVE AND ENTRY FOYER TO THE BREEZEWAY. NEC | | | 210.50 | | | THE AMPACITY OF THE CONDUCTORS TO THE GENERATOR SHALL | | | NOT BE LESS THAN 115% OF THE NAMEPLATE CURRENT RATING | | | OF THE GENERATOR. 1/0 CONDUCTORS ARE TOO SMALL. NEC | | | 445.13 | | | PROVIDE AN EQUIPMENT GROUND FOR THE GENERATOR FEED. NEC | | | T. 250.122 | | | | | | ROBERT LECKY, ELECTRICAL PLAN REVIEW, 561-805-6718 | | | | | | |
|