Plan Review Notes
Plan Review Notes For Permit 11020061
Permit Number 11020061
Review Stop E
Sequence Number 1
Notes
Date Text
2011-03-02 12:39:55VERIFY THE AVAILABLE FAULT CURRENT IS LESS THAN 10,000
 AMPS. NEC 110.9
 PROVIDE AN INTER SYSTEM BONDING STRIP AT ELECTRIC
 SERVICE. NEC 250.94
 3/0 CONDUCTORS ARE REQUIRED FOR FEEDERS PROTECTED WITH
 200 AMPERE BREAKER. NEC T. 310.16
 PANEL ???A??? (POOL) REQUIRES A #3 FEEDER CONDUCTOR
 WITH #8 GROUNDS. NEC T 310.16
 A GFCI PROTECTED RECEPTACLE IS REQUIRED TO SERVE CU #1
 AND #2. NEC 210.63
 SEVERAL RECEPTACLES REQUIRE LABELING FOR GFCI
 PROTECTION. THESE ARE LOCATED ON THE WEST PORCH, EAST
 PORCH AND KITCHENETTE. NEC 210.8
 ADDITIONAL RECEPTACLES ARE REQUIRED IN THE FAMILY ROOM,
 KITCHEN ALCOVE AND ENTRY FOYER TO THE BREEZEWAY. NEC
 210.50
 THE AMPACITY OF THE CONDUCTORS TO THE GENERATOR SHALL
 NOT BE LESS THAN 115% OF THE NAMEPLATE CURRENT RATING
 OF THE GENERATOR. 1/0 CONDUCTORS ARE TOO SMALL. NEC
 445.13
 PROVIDE AN EQUIPMENT GROUND FOR THE GENERATOR FEED. NEC
 T. 250.122
  
 ROBERT LECKY, ELECTRICAL PLAN REVIEW, 561-805-6718
  
  