Plan Review Notes
Plan Review Notes For Permit 11020061
Permit Number 11020061
Review Stop B
Sequence Number 1
Notes
Date Text
2011-02-16 12:21:26NEW SINGLE RESIDENCE (R3) BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- ACCORDING TO 2009 REVISIONS SEC. R301.2.1.4.3(2)
 THIS BUILDING IS LOCATED ON EXPOSURE "C" AND ROOF
 SHEATHING UPLIFT AND ROOF TO WALL UPLIFT LOADS SHALL BE
 INCREASED BY 20%. STRUCTURAL PLANS TO INDICATE THE
 ADDITIONAL 20 PERCENT INCREASE AND PROVIDE
 SPECIFICATIONS SHOWING COMPLIANCE WITH THIS
 REQUIREMENT.
  
 2- FOR YOUR INFORMATION: PROPERTY IS LOCATED ON FLOOD
 ZONE A5. ELEVATION CERTIFICATES WILL BE REQUIRED DURING
 THE CONSTRUCTION AND AT THE END OF CONSTRUCTION.
  
 3- PLANS ARE STAMPED BY PALM BEACH COUNTY FOR IMPACT
 FEES. PROVIDE COPY OF PAID RECEIPT.
  
 4- PROVIDE COMPLETE SPECIFICATIONS AND UL LISTING FOR
 OUTDOOR FIREPLACE AS REQUIRED BY SEC. R1005 OF 2007
 FLORIDA RESIDENTIAL CODE.
  
 5- FIRST FLOOR BATHROOM TO HAVE DOORS THAT ALLOW 29"
 MIN. CLEAR OPENING AS REQUIRED BY SEC. 11-11.1 OF 2007
 FBC.
  
 6- A) PROVIDE WINDOW CUT SHEETS FOR EGRESS WINDOWS
 (3'X5' DOUBLE HUNG WINDOWS) SHOWN ON BEDROOMS #2 TO
 VERIFY CLEAR OPENING SIZE OF 5.7S.F. AS REQUIRED BY
 SEC. R310.1.1.
  
 B) PROVIDE PRODUCT APPROVAL AND COMPLETE SPECIFICATIONS
 AND CUT SHEETS FOR CUSTOM EGRESS WINDOW CALLED "AD"
 SHOWN ON BEDROOM #4. SEC. R310.
  
 C) PROVIDE PRODUCT APPROVAL FOR CUSTOM WINDOWS "AE" AND
 "H" AS SHOWN ON THE WINDOW SCHEDULE.
  
 D) BEDROOM #3 WINDOWS DON'T COMPLY WITH THE EGRESS
 REQUIREMENTS OF SEC. R310. REVISE AS REQUIRED.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) UNDERLAYMENT SYSTEM SPECIFIED ON SHEETS A3 AND A4
 FOR 5V CRIMP METAL ROOFING.
  
 B) SHINGLE ROOF SYSTEM AS SPECIFIED ON SHEETS A3 AND
 A4.
  
 C) SEALOFLEX WATERPROOFING SUBMITTED: (1) ARCHITECT TO
 REFER TO CURRENT NOA 10-0608.02 SUBMITTED. (2)
 ARCHITECT TO IDENTIFY WHICH SPECIFIC APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED. (3) ARCHITECT TO REVISE RAS
 117 CALCULATIONS SUBMITTED. NAIL ENHANCING AT CORNER
 AREAS CAN'T BE LESS THAN 4"O.C. SEE SEC. 8.1 OF RAS
 117. REVISE NAIL SPACING AS REQUIRED.
  
 D) GREEN RIVER CEDAR SHAKES AND SHINGLES NOA 06-1107.01
 SUBMITTED. CLARIFY IF USING SHINGLES OR SHAKES.
 ARCHITECT SPECIFIES SHINGLES BUT SIZE SPECIFIED IS FOR
 SHAKES. SEE ARCHITECTURAL ELEVATIONS, NOA SUBMITTED AND
 RAS 130 TABLE 1. REVISE/CLARIFY AS REQUIRED. ALSO,
 ARCHITECT TO REVIEW AND APPROVE IN WRITING NOA
 SUBMITTED.
  
 E) ARCHITECT TO REVIEW AND APPROVE IN WRITING UC3
 COPPER PANELS SUBMITTED.
  
 F) ENTRY DOOR AS SHOWN ON PLANS.
  
 G) GARAGE DOORS AS SHOWN ON PLANS.
  
 H) PRECAST LINTELS AS SHOWN ON PLANS.
  
 I) SHUTTERS AS SHOWN ON PLANS. AND, PROVIDE COMPLETE
 INSTALLATION SCHEDULE AND CLEARLY MARK ON SHUTTERS
 DRAWINGS SPECIFIC ANCHOR TYPE AND SPACING TO BE USED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.
  
 J) METAL LOUVERED PANELS SHOWN ON EXTERIOR ELEVATIONS
 BY THE PORCHES AREAS. AND, CLEARLY IDENTIFY PROPOSED
 INSTALLATION TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.
  
 8- ARCHITECT TO REVIEW AND APPROVE IN WRITING ALL
 PRODUCT APPROVALS. SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 9- SHEET S1:
 A) DESIGN PRESSURES SHOWN FOR ONE STORY BUILDING DON'T
 CORRESPOND TO EXPOSURE "C" WORST CASE SCENARIO. REVISE
 AS REQUIRED. REVISE NUMBERS SHOWN ON THE GRAPH AND
 NUMBERS SHOWN BELOW.
  
 B) SPECIFY ALL THE DESIGN LOADS INCLUDING THE ATTIC
 LIVE LOAD AS REQUIRED BY SEC. R301 AND TABLE R301.5 OF
 2007 FLORIDA RESIDENTIAL CODE.
 ALSO, SPECIFY ALL THE SECOND FLOOR LOADS ON MAIN HOUSE.
 SHEET S3 ONLY PROVIDE SPECIFICATIONS FOR THE GUEST
 HOUSE.
 ***NOTE: INCLUDE THE ADDITIONAL WEIGHT OF THE GYP-CRETE
 FLOOR UNDERLAYMENT. SEE NOTE ON SHEET A2.
  
 10- PROVIDE SOIL TEST REPORT. SEC. R401.4 2007 FLORIDA
 RESIDENTIAL CODE.
  
 11- SHEET S-4: REVISE ROOF SHEATHING DETAIL: REVISE
 ROOF SHEATHING NAILING SPECIFICATIONS. NEED TO SPECIFY
 MIN. 8D RING SHANK NAILS AS REQUIRED BY SEC.
 R803.2.3.1.
  
 12- SHEET SW1:
 A) UPDATE ASCE EDITION SPECIFIED ON STRUCTURAL NOTES.
 REFER TO ASCE 7-05 NOT 02.
  
 B) REVISE WIND DESIGN CRITERIA. REFER TO CORRECT
 BUILDING EXPOSURE "C".
  
 13- ENERGY CALCULATIONS:
 A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 B) REVISE TYPE OF ROOF SPECIFIED ON SECOND PAGE. SEE
 ARCHITECTURAL DRAWINGS FOR TYPE OF ROOFS TO BE USED.
  
 C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM.
 INCLUDING BUILDER NAME.
  
 14- ENERGY CALCULATIONS SPECIFY UNVENTED ATTIC. PROVIDE
 COMPLETE SPECIFICATIONS FOR TYPE OF INSULATION TO BE
 USED.
 ***NOTE: ARCHITEC TO REVIEW AND APPROVE IN WRITING ALL
 THE SPECIFICATIONIS PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712