| Date |
Text |
| 2011-02-17 13:29:44 | 8401 COCOPLUM SOUND LANE |
| | CLUBHOUSE/RECREATIONAL CENTER |
| | PERMIT #11020032 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | |
| | NO ADDRESS PROVIDED IN TITLEBLOCK. |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. |
| | NUMBERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT AND |
| | SHALL CONTRAST THE BACKGROUND (REFERENCE: SECTION |
| | 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE ??? NFPA |
| | 1). |
| | |
| | STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| | CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| | THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| | REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF |
| | DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA |
| | ADMINISTRATIVE CODE 69A-60.0081. |
| | |
| | EVERY ROOM CONSTITUTING AN ASSEMBLY OCCUPANCY SHALL |
| | HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A |
| | CONSPICUOUS LOCATION NEAR THE MAIN EXIT FROM THE ROOM. |
| | |
| | ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN AREA |
| | HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE |
| | PROVIDED WITH PANIC HARDWARE TO RELEASE THE DOOR LATCH |
| | OR LOCK. |
| | |
| | EGRESS DOORS FROM THE GAME ROOM AND FITNESS ROOM ARE |
| | REQUIRED TO BE SIDE-HINGED. |
| | |
| | PROVIDE ADDITIONAL INFORMATION FOR EXITS DISCHARGING AT |
| | POOL LANAI. THE CONSTANT RELOCATION OF TABLES, CHAIRS, |
| | ETC. ON THE POOL DECK WILL MAKE IT DIFFICULT TO KEEP |
| | THE EXIT DOORS FREE FROM OBSTRUCTIONS. EXITS SHALL |
| | TERMINATE DIRECTLY AT A PUBLIC WAY. DISCHARGE INTO |
| | YARDS, COURTS, OR OTHER OPEN SPACES SHALL PROVIDE ALL |
| | OCCUPANTS WITH SAFE ACCESS TO A PUBLIC WAY. |
| | |
| | PROVIDE TACTILE SIGNAGE AT EACH EXIT DOOR REQUIRING AN |
| | EXIT SIGN. |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHER IN RECYCLE ROOM 116. |
| | |
| | ONE HOUR FIRE SEPARATION FOR RECYCLE ROOM 116 SHALL |
| | EXTEND INTO SMALL ELECTRICAL CLOSET. |
| | |
| | SHOW FIRE HYDRANT(S) LOCATION AND FIRE LANE ON SITE |
| | PLAN. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |